B7AC Interface Units
Node Address Settings
Note
Baud Rate Setting
Note
216
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Node address setting:
DIP switch 1, pins 1 through 6
Baud rate setting:
DIP switch 1, pins 7 and 8
SW1
SW2
ON
ON
1
2 3 4 5 6 7 8
1
2 3 4 5 6 7 8
Node address
B7AC
setting
transmission
delay setting
Baud rate setting
The settings on DIP switch 2 are communications settings for the individual
B7AC Interface Unit. Refer to Settings on DIP Switch 2 on page 219 for details
on these settings.
The B7AC Interface Unit's node address is set with pins 1 through 6 of DIP
switch 1. Any node address within the setting range can be used as long as it
isn't already set on another node.
DIP switch setting
Pin 6
Pin 5
Pin 4
Pin 3
0
0
0
0
0
0
0
0
0
0
0
0
:
:
1
1
1
1
1
1
1
1
1
1
1
1
0: OFF, 1: ON
1. Refer to Appendix A Node Address Settings Table for a complete table of
DIP switch settings.
2. The Slave won't be able to participate in communications if the same node
address is used for the Master or another Slave node (node address du-
plication error).
Pins 7 and 8 of DIP switch 1 are used to set the baud rate as shown in the fol-
lowing table. (These pins are factory-set to OFF.)
Pin Settings
Pin 7
Pin 8
OFF
OFF
ON
OFF
OFF
ON
ON
ON
1. Always turn OFF the Slave's power supply (including the communications
power supply) before changing the baud rate setting.
2. Set the same baud rate on all of the nodes (Master and Slaves) in the Net-
work. Any Slaves with baud rates different from the Master's rate won't be
able to participate in communications. Furthermore, a node with an incor-
rect baud rate setting may cause communications errors between nodes
with correct baud rate settings.
DIP switch 1
Pins 1 to 6: Node address setting
Pins 7 to 8: Baud rate setting
DIP switch 2
Pins 1 to 3: B7AC transmission delay
Pins 4 to 5: Reserved (Always OFF)
Pins 6 to 8: B7AC communications error
B7AC communications
error signal setting
Reserved (Always OFF.)
Node address
Pin 2
Pin 1
0
0
0 (default)
0
1
1
1
0
2
0
1
61
1
0
62
1
1
63
Baud rate
125 kbps
250 kbps
500 kbps (default)
Not allowed.
Section 5-5
signal setting
:
: