Hardware Settings And Wiring; Devicenet Wireless Master Station Settings And Installation; Devicenet Wireless Slave Station Settings And Installation - Omron WD30-ME Operation Manual

Devicenet wireless units
Hide thumbs Also See for WD30-ME:
Table of Contents

Advertisement

Hardware Settings and Wiring

2-3

Hardware Settings and Wiring

2-3-1

DeviceNet wireless master station settings and installation

Settings
Installation
2-3-2

DeviceNet wireless slave station settings and installation

Settings
Terminating
resistor
installation
24
station and slave station 1, and the wireless master station and slave station
2.
Settings and wiring to be performed before turning on the power supply to the
system are explained in this section.
An example setting for a wireless master station is shown below. Refer to 4-1
DeviceNet Wireless Master Station Specifications for details concerning set-
ting procedures. In this example, Status is selected and IN/OUT = 512/512
points (32 words/32 words).
DeviceNet master unit
Model CS1W-DRM21
(NNODE=00)
DeviceNet Network
Wireless master
station
Model WD30-M
Use screws to firmly fix the wireless master station that has already been tem-
porarily installed. Refer to 4-1 DeviceNet Wireless Master Station Specifica-
tions for details.
Settings example for each wireless slave station are shown below. Refer to 4-
2 DeviceNet Wireless Slave Station Specifications for details concerning the
setting procedure.
In this example, the default settings should be used for all DeviceNet settings
apart from the node address. Refer to the "DeviceNet Slave Manual" for
details concerning the settings for each DeviceNet slave.
Terminating resistors are required not only for the wireless master station, but also on both ends
of the wireless slave stations' DeviceNet network.
SW3=bit6 ON
SW1=bit3 ON
WNODE=01
NNODE=10
Mode select switch = SET
Section 2-3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wd30-seWd30-se01Wd30-me01Wd30-at001

Table of Contents