Analog I/O Terminals
Output Status after
Communications Error
154
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
1- to 5-V Outputs
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog
voltage range of 1 to 5 V. The entire output range is 0.8 to 5.2 V.
Voltage
5.2 V
5 V
1 V
0.8 V
0 V
812C
0000 (0)
FFFF
(–300)
0- to 20-mA Outputs
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog
current range of 0 to 20 mA. The entire output range is 0 to 21 mA.
Current
21 mA
20 mA
0 mA
0000 (0)
FFFF
4- to 20-mA Outputs
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog
current range of 4 to 20 mA. The entire output range is 3.2 to 20.8 mA.
Current
20.8 mA
20 mA
4 mA
3.2 mA
0 V
812C
0000 (0)
FFFF
(–300)
Pins 9 and 10 of the DIP switch determine the status of the outputs after a
communications error occurs in DeviceNet communications.
Hold:
Maintains the previous output status.
Low:
Clears to the lower limit of the output signal range.
High:
Clears to the upper limit of the output signal range.
Section 4-8
Converted data
Hexadecimal
1770
189C
7FFF
(Decimal)
(6000)
(6300)
Converted data
Hexadecimal
1770
189C
7FFF
(Decimal)
(6000)
(6300)
Converted data
Hexadecimal
1770
189C
7FFF
(Decimal)
(6000)
(6300)