Omron DeviceNet CV Series Operation Manual page 55

Devicenet slaves
Table of Contents

Advertisement

Connecting Communications Cables to General-purpose Slaves
1,2,3...
38
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
1. Pull out the connector band from the Slave Unit.
2. Lift up the connector band.
3. Insert the connector into the Slave Unit.
4. Wrap the connector band around the connector and secure firmly.
Note Multidrop connectors cannot be secured.
Multi-drop Connections
• Multi-drop Connections with Accessory Connector (Thin Cables Only)
The connectors provided with the Units can be used for a multi-drop con-
nection as long as thin cables are being used, just insert both lines into
the same hole in the connector. Be sure to use crimp connectors on both
lines. The following illustration shows a multi-drop connection for a con-
nector without set screws.
When connecting two lines to the same hole, first place them together in one
pressure-welded terminal as shown below.
Pressure-welded terminal: Pheonix Contacts model AI-TWIN2X0.5-8WH
(product number 3200933)
Pressure-welding tool: Pheonix Contacts model UD6 (product number
1204436)
Slave
Connector band
Slave
Pressure-welded
Cables
terminal for 2 lines
Section 4-2