Cqm1 I/O Link Unit: Cqm1-Drt21 - Omron DeviceNet CV Series Operation Manual

Devicenet slaves
Table of Contents

Advertisement

CQM1 I/O Link Unit

4-10-2 CQM1 I/O Link Unit: CQM1-DRT21

Specifications
Components
CQM1 Word Allocation
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
The general specifications for the CQM1-DRT21 I/O Link Unit conform to
CQM1 specifications.
Item
Model number
CQM1-DRT21
Number of I/O points
16 inputs, 16 outputs (32 I/O points total)
Compatible PLCs
All CQM1 PLCs and all CQM1H PLCs.
Max. number of Units
11 Units max. with CQM1H-CPU51-E/61-E PLCs (512
points max.) or CQM1H-CPU11-E/21-E PLCs (256 points
max.)
7 Units max. with
CQM1-CPU4
Connection to previous models:
CQM1-CPU4
CQM1-CPU11-E/21-E: 3 Units max. (128 points max.)
Current consumption
Communications power: 40 mA max.
Internal circuits: 80 mA max. (5 V DC)
Weight
185 g max.
General Specifications
Conform to SYSMAC CQM1 specifications.
In the CQM1 PLCs, an I/O Link Unit is treated just like an I/O Unit with one
input word and one output word, so word allocation is identical to a standard I/
O Unit. Words are allocated from the left side of the PLC, beginning with IR
Specification
@
-EV1 PLCs (256 points max.)
@
-E: 5 Units max. (192 points max.)
(Refer to page 312.)
Indicators
(Refer to page 40.)
DIP switch
Pins 1 to 6: Node address
Pins 7 and 8: Baud rate
Pin 9: Reserved (Always OFF.)
Pin 10: Hold/Clear outputs for communications error
Communications connector
Section 4-10