Troubleshooting By Slave Unit Type - Omron ERT1 Series Operation Manual

Ethernet/ip slave units
Table of Contents

Advertisement

Troubleshooting
Problem
NS indicator remains not
lit and status does not
change.
NS indicator remains lit
green and status does
not change.
7-2-2

Troubleshooting by Slave Unit Type

Model
All Slave Units
The MS and NS indicators do not light green.
Slave Units with out-
Cannot hold outputs when communications
puts
errors occur.
Cannot clear outputs when communications
errors occur.
Slave Units with
There is a delay with the ON and OFF timing for
inputs
input values.
Slave Units with
The Unconnected Line Detection Status Flag
Unconnected Line
turned ON for an unused input.
Detection Function
The Unconnected Line Detection Status Flag
turned ON even though the sensor power sup-
ply was connected.
Slaves with Discon-
The Disconnected Line Detection Status Flag
nected Line Detec-
turned ON for an unused output.
tion
The Disconnected Line Detection Status Flag
turned ON even though the external load was
connected.
The Slave Unit is not participating in the network.
• Check that all Slave Unit connectors are connected correctly.
• Check that the Master Unit is operating correctly. If using an OMRON Master Unit, check the
Master Unit mode and the Slave Unit node addresses.
• If using a Master from another manufacturer, refer to the user's manual for that Master.
• Check that the communications cable is wired correctly.
• Check that the power supply cable and power supply are wired correctly and that the set-
tings are correct.
• Check connector wiring to make sure that the communications cable and power supply
cables are not disconnected.
Check the following items and take corrective measures based on the Master Unit indicator
display.
• Check that the Master Unit is operating correctly. Refer to the manual for the Master Unit.
• Check that the tag data links are set correctly.
• Reset the tag data links.
Problem
Cause and possible corrections
Refer to 7-2-1 Indicators Are Lit or Flashing
Red.
The Unit is set to clear outputs for communica-
tions errors.
Change the setting to hold outputs for commu-
nications errors.
Change the setting to clear outputs for commu-
nications errors.
An input filter may be set.
Set the input filter value to No Display.
Alternatively, change the input filter to an
appropriate value.
Unconnected line detection is enabled for an
unused input.
Disable unconnected line detection for that
input.
Current consumption is low.
(Output current: 3 mA max.)
Disable unconnected line detection for that
input (so that the unconnected line detection
function does not operate.)
Disconnected line detection is enabled for an
unused output.
Disable disconnected line detection for that out-
put.
Current consumption is low.
(Output current: 3 mA max.)
Disable disconnected line detection for that out-
put (so that the disconnected line detection
function does not operate.)
Section 7-2
Cause
79