TL1 Reference
Retrieve Commands

Retrieve Frequency Parameter

The Retrieve Frequency Parameter command reports the frequency threshold
settings for the specified input port. The settings for each time period (100, 1000,
and 10000 seconds) are reported on three separate lines for each input port.
If the TSG-3800 successfully receives the command, it returns the COMPLD
message. If the TSG-3800 does not successfully receive the command, it returns
the DENY message.
Command Syntax
Valid aid
Minimum User Level
Response Format
Example Command
Example Response

Retrieve MTIE Parameter

The Retrieve MTIE Parameter command reports the MTIE threshold settings for the
specified input port. The settings for each time period (100, 1000, and 10000
seconds) are reported on three separate lines for each input port.
If the TSG-3800 successfully receives the command, it returns the COMPLD
message. If the TSG-3800 does not successfully receive the command, it returns
the DENY message.
Command Syntax
Valid aid
Minimum User Level
408 TSG-3800 User's Guide
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
RTRV-PRMTR-FREQ:[tid]:[aid]:ctag;
INP, INPx, INPx[-y], ALL, <null>
2
<cr><lf><lf>
M^ctag^COMPLD<cr><lf>
^^^aid:FREQ,lim1,mod1,lim2,mod2,tmper<cr><lf>
where:
lim1 and lim2 are the threshold values
mod1 and mod2 are the alarm mode settings
[Fail|Alarm|Rept| Ignr]
tmper is 100|1000|10000
RTRV-PRMTR-FREQ:TSG::ctag;
TSG 02-09-10 19:00:19
M 13 COMPLD
^^^TSG:
;
RTRV-PRMTR-MTIE:[tid]:[aid]:ctag;
INP, INPx, INPx[-y], ALL, <null>
2