Frequency And Mtie Errors; Synchronization Diagnostic Tests - Symmetricom TSG-3800 Series User Manual

Timing signal generator
Table of Contents

Advertisement

Frequency and MTIE Errors

The TSG-3800 makes frequency and MTIE measurements between each input
signal and both of the Clock modules in use. Clocks, whether selected for providing
outputs or not, track the selected input reference. In tracking, their control values
are adjusted to follow that input. With an MTIE or frequency error, the source of
error is not always apparent. Any input or clock can cause the problem.
The history of each input signal's phase relationship to each clock and each
oscillator's control value provide valuable information for determining the source of
error.
When receiving an MTIE or frequency error, retrieve the control value history for the
clocks and the phase history for each input. Use the CLK CV T100 command for
listing the control value history and PHASE INP1.1 (or INP2.1) T100 command for
listing the phase history. Use
Note: This procedure assumes that two input signals and two clocks
are used.
The difference between minor and significant change varies with the
model of clock used. Contact Symmetricom Global Services if you
need assistance in making this determination.
Table 4-3. Synchronization Diagnostic Tests
Condition
1
Clock A selected for output.
INP1.1 and INP2.1 phase history shows minor or no change.
Clock A's control value shows significant change.
Clock B's control value shows only minor or no change.
2
Clock B selected for output.
INP1.1 and INP2.1 phase history shows minor or no change.
Clock A's control value shows only minor or no change.
Clock B's control value shows significant change.
3
INP1.1 phase history shows minor or no change.
INP2.1 phase history shows significant change.
Clock A's control value shows significant change.
Clock B's control value shows significant change.
4
INP1.1 phase history shows minor or no change.
INP2.1 phase history shows significant change.
Clock A's control value shows only minor or no change.
Clock B's control value shows only minor or no change.
12778474-002-2 Revision F – March 2004
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Table 4-3
as guidelines for tracing the error source.
Symptoms
Maintenance and Troubleshooting
Troubleshooting Guidelines
Probable
Source
Clock A
Clock B
INP1.1 input
signal
INP2.1 input
signal
TSG-3800 User's Guide 119