Retrieve Alarm Data; Retrieve Clock Data - Symmetricom TSG-3800 Series User Manual

Timing signal generator
Table of Contents

Advertisement

Minimum User Level
Example Command
Example Response

Retrieve Alarm Data

The Retrieve Alarm Data command reports the error and clear counts for the
specified error and aid.
If the TSG-3800 successfully receives the command, it returns the COMPLD
message. If the TSG-3800 does not successfully receive the command, it returns
the DENY message.
Command Syntax
Valid aid
Minimum User Level
Response Format
Example Command
Example Response

Retrieve Clock Data

The Retrieve Clock Data command reports the current 1-s and 100-s control values
and tau for the A and B clocks.
If the TSG-3800 successfully receives the command, it returns the COMPLD
message. If the TSG-3800 does not successfully receive the command, it returns
the DENY message.
Command Syntax
Valid aid
Minimum User Level
12778474-002-2 Revision F – March 2004
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
2
RTRV-CONF:TSG:CLKA:ctag;
TSG 02-09-10 19:00:19
M 1 COMPLD
"CLKA:ST2RUB,Config Not Available"<cr><lf>
RTRV-DATA-AIS:[tid]:[aid]:ctag;
RTRV-DATA-BPV:[tid]:[aid]:ctag;
RTRV-DATA-CRC:[tid]:[aid]:ctag;
RTRV-DATA-LOS:[tid]:[aid]:ctag;
RTRV-DATA-OOF:[tid]:[aid]:ctag;
INP, INPx, INPx[-y], ALL, <null>
1
<cr><lf><lf>
M^ctag^COMPLD<cr><lf>
^^^aid:prmtr,ercnt,clcnt<cr><lf>
RTRV-DATA-AIS:TSG:INP2:ctag;
TSG 02-09-10 19:00:19
M 13 COMPLD
^^^TSG:AIS,1,5
RTRV-DATA-CLK:[tid]:[aid]:ctag;
CLK, CLKA, CLKB, ALL, <null>
2
TL1 Reference
Retrieve Commands