Autonomous Reports

For an unsuccessfully completed input command (command-denied response), the
format of the response is:
M^<CTAG>^DENY
Autonomous Reports
Autonomous reports are generated when the TSG-3800 detects an alarm condition
or a status change. The alarm status is updated whenever the alarm status
changes, including whenever a user sets or clears an alarm. The message appears
on the Comm port configured for TL1.
The response message line has the following format:
<cr><lf><lf>
"[
^^^
><lf>
;
The alarm status report has the following format:
<cr><lf><lf>
"[
^^^
^^^sid^ocrdat^ocrtim<cr><lf>
almcde^atag^REPT^mod1[^mod2]<cr><lf>
;
where:
<ntfcncde> is a two-letter code as described in
Table C-2. Notification Codes
Alarm Code
CR
MJ
MN
CL
NA
376 TSG-3800 User's Guide
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
aid]:ntfcncde,condtype,srveff,ocrdat,octrm[:condscr]
aid]:ntfcncde,condtype,condscr
Type of Alarm
Critical Alarm
Major Alarm
Minor Alarm
Cleared Alarm
Non-alarm event
"
<cr><lf>
Table
C-2.
12778474-002-2 Revision F – March 2004
"