7. PARAMETERS
No./
Setting
symbol/name
digit
PL04
_ _ x _ For manufacturer setting
*LIT2
_ x _ _
Linear servo
x _ _ _ [AL. 42 Servo control error] detection function controller reset condition selection
motor/DD
0: Reset disabled (reset by powering off/on enabled)
motor
1: Reset enabled
function
selection 2
PL05
Set a position deviation error detection level of the servo control error detection.
LB1
When the deviation between a model feedback position and actual feedback position
is larger than the setting value, [AL. 42 Servo control error] will occur.
Position
deviation
However, when "0" is set, the level varies depending on the operation mode in
error
[Pr. PA01].
detection
Linear servo motor: 50 mm
level
Direct drive motor: 0.09 rev
Setting range: 0 to 1000
PL06
Set a speed deviation error detection level of the servo control error detection.
LB2
When the deviation between a model feedback speed and actual feedback speed is
larger than the setting value, [AL. 42 Servo control error] will occur.
Speed
deviation
However, when "0" is set, the level varies depending on the operation mode in
error
[Pr. PA01].
detection
Linear servo motor: 1000 mm/s
level
Direct drive motor: 100 r/min
Setting range: 0 to 5000
PL07
Set a torque/thrust deviation error detection level of the servo control error detection.
LB3
When the deviation between a current command and current feedback is larger than
the setting value, [AL. 42.3 Servo control error by torque/thrust deviation] will occur.
Torque/thrust
deviation error
detection level
Setting range: 0 to 1000
PL08
_ _ _ x Magnetic pole detection method selection
*LIT3
0: Position detection method
Linear servo
4: Minute position detection method
motor/DD
_ _ x _ For manufacturer setting
motor
_ x _ _ Magnetic pole detection - Stroke limit enabled/disabled selection
function
0: Enabled
selection 3
1: Disabled
x _ _ _ For manufacturer setting
PL09
Set a direct current exciting voltage level during the magnetic pole detection.
LPWM
If [AL. 32 Overcurrent], [AL. 50 Overload 1], or [AL. 51 Overload 2] occurs during the
magnetic pole detection, decrease the setting value.
Magnetic pole
detection
If [AL. 27 Initial magnetic pole detection error] occurs during the magnetic pole
voltage level
detection, increase the setting value.
Setting range: 0 to 100
PL17
_ _ _ x Response selection
LTSTS
Set a response of the minute position detection method.
Magnetic pole
When reducing a travel distance at the magnetic pole detection, increase the setting
detection -
value.
Minute
Refer to table 7.12 for settings.
position
_ _ x _ Load to motor mass ratio/load to motor inertia ratio selection
detection
Select a load to mass of the linear servo motor primary-side ratio or load to mass of the
method -
direct drive motor inertia ratio used at the minute position detection method. Set a
Function
closest value to the actual load.
selection
Refer to table 7.13 for settings.
_ x _ _ For manufacturer setting
x _ _ _
Function
7 - 74
www.kavrammuhendislik.com.tr
Control mode
Initial
value
[unit]
0h
0h
0h
0
[mm]/
[0.01
rev]
0
[mm/s]/
[r/min]
100
[%]
0h
1h
0h
0h
30
[%]
0h
0h
0h
0h