112 Application macros
Factory macro
The Factory macro is suited to relatively straightforward speed control applications such
as conveyors, pumps and fans, and test benches.
The drive is speed-controlled with the reference signal connected to analog input AI1.
The start/stop commands are given through digital input DI1; running direction is
determined by DI2. This macro uses control location EXT1.
Faults are reset through digital input DI3.
DI4 switches between acceleration/deceleration time sets 1 and 2. The acceleration
and deceleration times, as well as ramp shapes, are defined by parameters 23.12...23.19.
DI5 activates constant speed 1.
■
Default parameter settings for the Factory macro
The default parameter settings for the Factory macro are listed in chapter
listing (page
136).
■
Default control connections for the Factory macro
Connection
XPOW External power input
XAI Reference voltage and analog inputs
XAO Analog outputs
XD2D Drive-to-drive link
Term
+24VI
GND
1
+24VI
2
GND
+VREF
1
+VREF
-VREF
2
-VREF
3
AGND
AGND
AI1+
4
AI1+
AI1-
5
AI1-
AI2+
6
AI2+
7
AI2-
AI2-
AO1
1
AO1
AGND
2
AGND
3
AO2
AO2
AGND
4
AGND
B
1
B
A
2
A
BGND
3
BGND
Description
24 V DC, 2 A
10 V DC, R L 1...10 kohm
-10 V DC, R L 1...10 kohm
Ground
Speed reference
0(2)...10 V, R in > 200 kohm
By default not in use.
0(4)...20 mA, R in = 100 ohm
Motor speed rpm
0...20 mA, R L < 500 ohm
Motor current
0...20 mA, R L < 500 ohm
Master/follower, drive-to-drive or embedded
fieldbus interface connection
Parameter