A3-22
lnstallation
Connecting Electrical
Seruice
Follow
this procedure to connect electrical service to your unit.
1.
Open
the electrical
enclosure.
Refer
to
Opening the
Electrical
Enclosure.
2.
See Figure A
3-13.
Locate
the identification plate on your unit.
54321
Ci]"HHHH
o
o
41306904
Fig. A
3-13
Location
of ldentification
Plate
CAUTION:
Risk of
equipment
damage.
Operate
the unit only
at
480
VAC.
3.
See Figure A
3-14.
Make sure
the VOTTS (ac) portion (1) of the
identification plate contains the
following voltage information:
3AC 480
V.
4.
Size
your electrical service line based on the maximum amperage
shown in
the AMPS (max.) portion (2) of the identification
plate. The
line must
also meet local electrical code requirements.
@
TEMP:
NORDSON CORP.
,
AMHERST, OHIO,
UNIT NO.
SERIAL NO.
POWER REOUI
VOLTS (ac)
HZ
o
AMPS (Max.)
WATIS
(Max.)
1
2
alenARqa
Fig. A
3-14
Unit
ldentification
Plate
1.
VOLTS (ac) portion
2.
AMPS
(max.) portion
I
A3
EN-04-[3V-X-4XXVI-l
3
41-3000y
lssued 5/00
@000
Nordson