Setting Calendar/Clock Using WindLDR

Before using the clock cartridge for the first time, the calendar/clock data in the clock cartridge must be set using
or executing a user program to transfer correct calendar/clock data from special data registers allocated to the calendar/
clock. Once the calendar/clock data is stored, the data is held by the backup battery in the clock cartridge.
1. Select Online from the
2. From the Online menu, select PLC Status. The MicroSmart PLC Status dialog box is displayed. The current calendar/
clock data is read out from the clock cartridge and displayed in the Calendar box.
3. Click the Change button in the Calendar box. The Set Calendar and Time dialog box comes up with the date and time
values read from the computer internal clock.
4. Click the Down Arrow button on the right of Calendar, then a calendar is displayed where you can change the year,
month, and date. Enter or select new values.
5. To change hours and minutes, click in the Time box, and type a new value or use the up/down keys. When new values
are entered, click the OK button to transfer the new values to the clock cartridge.

Setting Calendar/Clock Using a User Program

Another way of setting the calendar/clock data is to store the values in special data registers dedicated to the calendar and
clock and to turn on special internal relay M8016, M8017, or M8020. Data registers D8015 through D8021 do not hold the
current values of the calendar/clock data but hold unknown values before executing a user program.
Special Data Registers for Calendar/Clock Data
Data Register No.
D8008
D8009
D8010
D8011
D8012
D8013
D8014
D8015
D8016
D8017
D8018
D8019
D8020
D8021
Note: The day of week value is assigned for both current and new data as follows:
0
1
Sunday
Monday
menu bar, then select Monitor. The screen display changes to the monitor window.
WindLDR
Data
Year (current data)
Month (current data)
Day (current data)
Day of week (current data)
Hour (current data)
Minute (current data)
Second (current data)
Year (new data)
Month (new data)
Day (new data)
Day of week (new data)
Hour (new data)
Minute (new data)
Second (new data)
2
Tuesday
Wednesday
« FC4A M
ICRO
15: W
Value
0 to 99
1 to 12
1 to 31
0 to 6 (Note)
0 to 23
0 to 59
0 to 59
0 to 99
1 to 12
1 to 31
0 to 6 (Note)
0 to 23
0 to 59
0 to 59
3
4
Thursday
S
U
'
M
»
MART
SER
S
ANUAL
P
EEK
ROGRAMMER
Read/Write
500 ms or one scan time
Read only
whichever is larger
Write only
Not updated