AC Input Module Specifications
Type No.
Input Points and Common Lines
Terminal Arrangement
Rated Input Voltage
Input Voltage Range
Rated Input Current
Input Type
Input Impedance
Turn ON Time
Turn OFF Time
Isolation
External Load for I/O Interconnection
Signal Determination Method
Effect of Improper Input Connection
Connector on Mother Board
Connector Insertion/Removal Durability
Internal Current Draw
Weight
Input Operating Range
The input operating range of the Type 1, 2, 3 (IEC 61131-2)
input module is shown below:
FC4A-N08A11
132
100
79
74
20
0
1
2
4
5
Input Current (mA)
8 points in 2 common lines
See Input Module Terminal Arrangement on page 2-29.
100 to 120V AC (50/60 Hz)
85 to 132V AC
17 mA/point (120V AC, 60 Hz)
AC input, Type 2 (IEC 61131-2)
0.8 kΩ (60 Hz)
25 ms
30 ms
Between input terminals in the same common: Not isolated
Between input terminals in different commons: Isolated
Between input terminals and internal circuits:
Not needed
Static
If any input exceeding the rated value is applied, permanent damage may be
caused.
MC1.5/11-G-3.81BK (Phoenix Contact)
100 times minimum
60 mA (5V DC)
All Inputs ON
0 mA (24V DC)
30 mA (5V DC)
All Inputs OFF
0 mA (24V DC)
80g
ON Area
Transition
Area
OFF Area
13
17
« FC4A M
ICRO
FC4A-N08A11
Input Internal Circuit
FC4A-N08A11
Input
COM
Input Usage Limits
When using the FC4A-N08A11, all inputs can be
turned on simultaneously at 55°C, input voltage
132V AC.
132
120
102
0
0
S
U
'
M
»
MART
SER
S
ANUAL
2: M
S
ODULE
PECIFICATIONS
Photocoupler isolated
480 kΩ
220Ω
0.33 µF
55°C
50
100
Input Simultaneous ON Ratio (%)
2-25