BCC (Block Check Character)
The
has an automatic BCC calculation function to detect a communication error in incoming data. If a BCC
MicroSmart
code is designated in the receive format of a RXD instruction, the
ing position through the position immediately preceding the BCC and compares the calculation result with the BCC code
in the received incoming data. The start position for the BCC calculation can be specified from the first byte through the
15th byte. The BCC, calculated in either XOR or ADD, can be 1 or 2 digits.
Upgraded CPU modules can also use ADD-2comp, Modbus ASCII, and Modbus RTU to calculate the BCC.
When an end delimiter is not used in the RXD instruction, the BCC code must be positioned at the end of the receive for-
mat designated in Source 1 operand. When an end delimiter is used, the BCC code must be immediately before or after the
end delimiter. The
MicroSmart
mat to calculate and compare the received BCC code with the BCC calculation results.
BCC Calculation Start Position
The start position for the BCC calculation can be specified from the first byte through the 15th byte. The BCC is calculated
for the range starting at the designated position up to the byte immediately before the BCC of the receive data.
Example: Received data consists of 17 bytes plus 2 BCC digits.
(1) Calculation start position = 1
1st
2nd
3rd
STX
"A"
"B"
(2) Calculation start position = 2
1st
2nd
3rd
STX
"A"
"B"
BCC Calculation Formula
BCC calculation formula can be selected from XOR (exclusive OR) or ADD (addition) operation. ADD-2comp, Modbus
ASCII, and Modbus RTU can also be selected for the upgraded CPU modules.
Example: Incoming data consists of 41h, 42h, 43h, 44h, and 45h.
(1) BCC Calculation formula = XOR
Calculation result = 41h ⊕ 42h ⊕ 43h ⊕ 44h ⊕ 45h = 41h
(2) BCC Calculation formula = ADD
Calculation result = 41h + 42h + 43h + 44h + 45h = 14Fh → 4Fh (Only the last 1 or 2 digits are used as BCC.)
(3) BCC calculation formula = ADD-2comp
Calculation result = B1
(4) BCC calculation formula = Modbus ASCII
Calculation result = A8
(5) BCC calculation formula = Modbus RTU
Calculation result = 91h 50h
reads a specified number of BCC digits in the incoming data according to the receive for-
4th
5th
6th
"C"
"D"
"E"
BCC calculation range
4th
5th
6th
"C"
"D"
"E"
BCC calculation range
« FC4A M
ICRO
17: U
SER
calculates a BCC value for a specified start-
MicroSmart
15th
16th
17th
18th
19th
"0"
CR
LF
BCC
BCC
BCC
(2 digits)
15th
16th
17th
18th
19th
"0"
CR
LF
BCC
BCC
BCC
(2 digits)
S
U
'
M
»
MART
SER
S
ANUAL
C
I
OMMUNICATION
NSTRUCTIONS
17-21