Timing Chart for Reversible Control with Single Pulse Output
This program demonstrates a timing chart of the RAMP instruction when reversible control is enabled with single pulse
output.
RAMP
D200
I0
Control Direction D205
Steady Pulse Frequency
Initial Pulse Frequency
Control Direction Output Q1
Pulse Output ON M50
Pulse Output Complete M51
Pulse Output Status M52
• When input I0 is turned on, RAMP generates output pulses starting at the initial frequency designated by the value
stored in data register D202. While the output pulses are sent out from output Q0, internal relay M50 remains on.
• Operation modes 0 through 2: The pulse frequency increases according to the frequency change rate value stored
in data register D203.
• Operation mode 3: The pulse frequency increases as long as the frequency change time stored in data register
D203.
• While the output pulse frequency is on the increase, internal relay M52 remains on.
• Depending on the control direction designated by the value stored in data register D205, control direction output
Q1 turns off or on while D205 stores 0 (forward) or 1 (reverse), respectively.
• When the output pulse frequency reaches the steady pulse frequency designated by the value stored in data regis-
ter D201, internal relay M52 turns off. When the output pulse frequency starts to decrease, internal relay M52
turns on again.
• When the quantity of generated output pulses reaches the preset value designated by data registers D206 and
D207, RAMP stops generating output pulses. Then internal relay M50 and M52 turn off, and internal relay M51
turns on.
• If the parameter values in D200 through D207 (except for D204) are changed while generating output pulses, the
change takes effect when start input I0 is turned on for the next cycle.
• If the value stored in D204 is changed after start input I0 has been turned on, the change can take effect only
after the CPU starts again.
• If start input I0 is turned off before reaching the preset value, RAMP stops generating output pulses immediately,
then internal relay M50 turns off and internal relay M51 turns on. When input I0 is turned on again, RAMP restarts
to generate output pulses for another cycle, starting at the initial pulse frequency.
D204 = 1 (reversible control with single pulse output)
S1
D1
M50
Start Input I0
Output Pulse Q0
« FC4A M
0 (Forward)
S
U
'
M
ICRO
MART
SER
S
ANUAL
20: P
ULSE
1 (Reverse)
»
I
NSTRUCTIONS
20-19