IDEC FC4A-C10R2 User Manual page 463

Fc4a series microsmart micro programmable logic controller
Table of Contents

Advertisement

Status Information
The status information is allocated to AS-Interface internal relays M1940 through M1997. These internal relays are used to
monitor the status of the AS-Interface bus. If an error occurs on the bus, you can also confirm the error with the status
LEDs on the front of the AS-Interface master module in addition to these status internal relays.
Status Information Internal Relays
Internal Relays
M1940
Config_OK
M1941
LDS.0
M1942
Auto_Address_Assign
M1943
Auto_Address_Available
M1944
Configuration
M1945
Normal_Operation_Active
M1946
APF/not APO
M1947
Offline_Ready
M1950
Periphery_OK
M1951-M1957
M1960
Data_Exchange_Active
M1961
Off-line
M1962
Connected Mode
M1963-M1997
M1940 Config_OK
M1940 indicates the configuration status. M1940 goes on when the permanent configuration data (PCD) stored in the
AS-Interface master module EEPROM matches the configuration data image (CDI). When configuration is changed, e.g. a
new slave is added or a slave fails, M1940 goes off. Then, the FLT LED goes on.
M1941 LDS.0
M1941 is used to check for the presence of a slave with address 0 on the AS-Interface bus. M1941 goes on when a slave
with address 0 (the factory setting) is detected on the AS-Interface bus in normal protected mode or protected mode, or
when a slave address is changed to 0 while the AS-Interface master module is in normal protected mode.
M1942 Auto_Address_Assign
M1942 indicates that the auto addressing function is enabled. The default setting is "enabled," and M1942 is normally on.
This setting can be changed using the ASI commands Enable Auto Addressing and Disable Auto Addressing.
Note: When the auto addressing function is enabled at the AS-Interface master module and a slave fails, you can replace
the slave with a new slave which has the same identification codes without stopping the AS-Interface bus.
If the replacement slave is assigned the same address and has the same identification codes as the failed slave, the
replacement slave is automatically added to the LDS (list of detected slaves) to continue operation. If the assigned
address or the identification codes of the replacement slave are different from the failed slave, the FLT LED will go on.
When replacing a failed slave with a new slave which is assigned address 0 (factory setting) and has the same identifica-
tion codes, the new slave will be assigned the address of the failed slave and added to the LDS and LAS (list of active
slaves). If the identification codes of the replacement slave are different from the failed slave, the FLT LED will go on.
The auto addressing function for a replacement slave works only when one slave has failed. This function cannot be used
to replace multiple slaves.
Status
Configuration is complete.
Slave address 0 is detected on
the AS-Interface bus.
Auto addressing is enabled.
Auto addressing is ready.
Configuration mode is enabled.
Normal protected mode is
enabled.
AS-Interface power supply failure.
Normal protected offline is
enabled.
Peripheral devices are normal.
(reserved)
Data exchange is enabled.
Command to go to normal pro-
tected offline was issued by the
pushbutton or WindLDR.
Connected mode is enabled.
(reserved)
« FC4A M
ICRO
28: AS-I
NTERFACE
Description
ON
S
U
'
M
»
MART
SER
S
ANUAL
M
C
ASTER
OMMUNICATION
OFF
Configuration is incomplete.
Slave address 0 is not detected on
the AS-Interface bus.
Auto addressing is disabled.
Auto addressing is not ready.
Other than configuration mode.
Other than normal protected mode.
AS-Interface power supply is normal.
Other than normal protected offline.
Peripheral devices are abnormal.
Data exchange is prohibited.
Command to go to normal protected
offline was not issued.
Local mode is enabled.
28-23