28: AS-I
M
NTERFACE
Error Messages
When an error is returned from the AS-Interface master module,
and their meanings are given below.
Error Code
1
2
7
8
When a reply message is not returned from the AS-Interface master module, the following error message will be dis-
played.
28-34
C
ASTER
OMMUNICATION
An error was found on the expansion I/O bus.
While the AS-Interface master module was in offline mode, attempt was made to perform auto
configuration or manual configuration.
An incorrect command was sent.
While slave address 0 existed on the bus, attempt was made to perform auto configuration or
manual configuration.
The AS-Interface master module is in local mode.
The slave you are trying to change does not exist.
A slave of the designated new address already exists.
While a standard slave was set at A address, attempt was made to set an A/B slave at B
address of the same number.
While an A/B slave was set at B address, attempt was made to set a standard slave at A
address of the same number.
Attempt was made to change the parameters of a slave which did not exist.