Alt (Alternate Output) - IDEC FC4A-C10R2 User Manual

Fc4a series microsmart micro programmable logic controller
Table of Contents

Advertisement

14: D
C
ATA
ONVERSION

ALT (Alternate Output)

ALT
SOTU
Applicable CPU Modules
FC4A-C10R2/C
FC4A-C16R2/C
Valid Operands
Operand
D1 (Destination 1)
For the valid operand number range, see pages 6-1 and 6-2.
Since the ALT instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction must
be used.
Example: ALT
ALT
SOTU
I0
ON
Input I0
OFF
ON
Output Q0
OFF
14-14
I
NSTRUCTIONS
When input is turned on, output, internal relay, or shift register bit designated by
D1
D1 is turned on and remains on after the input is turned off.
*****
When input is turned on again, the designated output, internal relay, or shift reg-
ister bit is turned off.
The ALT instruction must be used with a SOTU or SOTD instruction, otherwise the
designated output, internal relay, or shift register bit repeats to turn on and off in
each scan.
FC4A-C24R2/C
Function
Bit to turn on and off
When input I0 is turned on, output Q0 designated by operand D1 is turned on and
D1
remains after input I0 is turned off.
Q0
When input I0 is turned on again, output Q0 is turned off.
« FC4A M
FC4A-D20K3/S3
I
Q
X
S
U
'
M
ICRO
MART
SER
S
ANUAL
FC4A-D20RK1/RS1 & FC4A-D40K3/S3
X
M
R
T
C
D
Constant
X
X
— — —
»
Repeat