10. Select maximum and minimum values.
For analog input values, when Optional range is selected for the Data Type, designate the analog input data minimum and
maximum values which can be –32,768 through 32,767.
In addition, when using resistance thermometers (Pt100, Pt1000, Ni100, or Ni1000) with the Celsius or Fahrenheit Data
Type and the ×100 scale, select the analog input data minimum value from 0 or another value in the pull-down list. The
maximum value is changed automatically according to the selected minimum value.
For analog output values, when Optional range is selected for the Data Type, designate the analog output data minimum
and maximum values which can be –32,768 through 32,767.
11. View the data register numbers allocated to Data and Status.
Analog I/O Data
Stores the digital data converted from an analog input
Data
signal or converted into an analog output signal.
Designated as source operand S4 (process variable)
of the PID instruction.
Analog I/O Operating Status
Status
Stores an analog I/O operating status code.
See pages 24-13 and 24-15.
12. Click the OK button to save changes and exit the Configure Parameter dialog box.
13. Repeat the same steps for other slots.
14. When finished, click the OK button to save changes and exit the Set Analog Module Parameters dialog box.
24-6
Parameter
« FC4A M
ICRO
END Refresh Type
Data registers are automatically allocated depending
on the slot where the analog I/O module is mounted.
Ladder Refresh Type
Data registers are automatically allocated depending
on the number designated in the DR Allocation Num-
ber field.
S
U
'
M
»
MART
SER
S
ANUAL
DR Allocation

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents