Zrn1 (Zero Return 1); Zrn2 (Zero Return 2) - IDEC FC4A-C10R2 User Manual

Fc4a series microsmart micro programmable logic controller
Table of Contents

Advertisement

20: P
I
ULSE
NSTRUCTIONS

ZRN1 (Zero Return 1)

ZRN
1
*****

ZRN2 (Zero Return 2)

ZRN
2
*****
Note: The ZRN1 and ZRN2 instructions can be used only once in a user program. When ZRN1 or ZRN2 is not used, unused
output Q0 or Q1 can be used for another pulse instruction or ordinary output.
Applicable CPU Modules
FC4A-C10R2/C
FC4A-C16R2/C
Valid Operands
Operand
S1 (Source 1)
S2 (Source 2)
D1 (Destination 1)
Source operand S1 (control register) uses 5 data registers starting with the operand designated as S1. Data registers D0
through D1295 and D2000 through D7995 can be designated as S1. For details, see the following pages.
Source operand S2 (deceleration input) can designate inputs I0 through I307 and internal relays M0 through M1277. Spe-
cial internal relays cannot be designated as S2.
Destination operand D1 (status relay) uses 2 internal relays starting with the operand designated as D1. Internal relays M0
through M1270 can be designated as D1. Special internal relays cannot be designated as D1. For details, see page 6-2.
Source Operand S1 (Control Register)
Store appropriate values to data registers starting with the operand designated by S1 before executing the ZRN instruction
as required, and make sure that the values are within the valid range. Operand S1+4 is for read only.
Operand
S1+0
Initial operation mode
S1+1
Initial pulse frequency
S1+2
Creep operation mode
S1+3
Creep pulse frequency
S1+4
Error status
20-24
S1
S2
D1
*****
*****
S1
S2
D1
*****
*****
FC4A-C24R2/C
Function
Control register
Deceleration input
Status relay
Function
0: 10 to 1,000 Hz
1: 100 to 10,000 Hz
2: 1,000 to 20,000 Hz
When S1+0 (initial operation mode) = 0 or 1: 1 to 100 (%)
(1% to 100% of the maximum frequency of selected mode S1+0)
When S1+0 (initial operation mode) = 2: 1 to 20 (×5%)
(5% to 100% of the maximum frequency of selected mode S1+0)
0: 10 to 1,000 Hz
1: 100 to 10,000 Hz
2: 1,000 to 20,000 Hz
When S1+2 (creep operation mode) = 0 or 1: 1 to 100 (%)
(1% to 100% of the maximum frequency of selected mode S1+2)
When S1+2 (creep operation mode) = 2: 1 to 20 (×5%)
(5% to 100% of the maximum frequency of selected mode S1+2)
0 to 2
« FC4A M
When input is on, the ZRN1 instruction sends out a pulse output of a
predetermined high frequency from output Q0. When a deceleration
input turns on, the output frequency decreases to a creep frequency.
When the deceleration input turns off, the ZRN1 instruction stops gener-
ating output pulses.
The output pulse width ratio is fixed at 50%.
When input is on, the ZRN2 instruction sends out a pulse output of a
predetermined high frequency from output Q1. When a deceleration
input turns on, the output frequency decreases to a creep frequency.
When the deceleration input turns off, the ZRN2 instruction stops gener-
ating output pulses.
The output pulse width ratio is fixed at 50%.
FC4A-D20K3/S3
I
— — — — — —
— ▲ — — — —
X
— — ▲ — — — —
Description
S
U
'
M
ICRO
MART
SER
S
ANUAL
FC4A-D20RK1/RS1 & FC4A-D40K3/S3
X
Q
M
R
T
C
D
X
»
Constant
Repeat
R/W
R/W
R/W
R/W
R/W
R