IDEC FC4A-C10R2 User Manual page 400

Fc4a series microsmart micro programmable logic controller
Table of Contents

Advertisement

24: A
I/O C
NALOG
ONTROL
END Refresh Type
The operating status of each analog input channel is stored to a data register, such as D761 or D767, allocated to analog
input channel 1 or 2 on analog module number 1 through 7 depending on the mounting position.
The analog input operating status data is updated whether the CPU module is running or stopped. When the CPU module
is running, the update occurs at the END processing of every scan or 10 ms, whichever is longer. When the CPU module is
stopped, the update occurs every 10 ms.
Status Code
0
Normal operation
1
Converting data (during the first data conversion after power-up)
2
Initializing
3
Invalid parameter or analog input channel not available on the installed analog module
4
Hardware failure (external power supply failure)
5
Incorrect wiring (input data over valid range)
6
Incorrect wiring (input data below valid range or current loop open)
Ladder Refresh Type
The operating status of each analog input channel is stored to a data register determined by the data register number
selected in the Configure Parameters dialog box of the ANST macro.
Operating Status Bit
0
Bit 0
1
0
Bit 1
1
0
Bit 2
1
0
Bit 3
1
0
Bit 4
1
Bit 5 to Bit 15
0
24-14
Analog Input Operating Status (END refresh type)
Analog Input Operating Status (Ladder refresh type)
Operating status bit
Parameter bit
External power supply bit
Maximum value over bit
Minimum value over bit
Reserved
« FC4A M
ICRO
Normal operation
Initializing, changing configuration, hardware initialization error
Parameter configuration normal
Parameter configuration error
External power supply normal
External power supply error
Within the maximum value
Maximum value over error
Within the minimum value
Minimum value under error
Normal operation
S
U
'
M
»
MART
SER
S
ANUAL