IDEC FC4A-C10R2 User Manual page 166

Fc4a series microsmart micro programmable logic controller
Table of Contents

Advertisement

6: A
N
LLOCATION
UMBERS
Slim Type CPU Modules
Operand
Input (I)
Expansion Input (I)
Output (Q)
Expansion
Output (Q)
Internal Relay (M)
AS-Interface
Internal Relay (M)
Special Internal
Relay (M)
Shift Register (R)
Timer (T)
Counter (C)
Data Register (D)
AS-Interface Data
Register (D)
Expansion Data
Register (D)
Special Data
Register (D)
Notes:
The least significant digit of input, output, internal relay, and special internal relay operand number is an octal number (0
through 7). Upper digits are decimal numbers.
The allocation numbers of expansion inputs and outputs start with I30 and Q30, respectively.
Note that input and output allocation numbers are not continuous between the CPU module and expansion I/O modules.
A maximum of 7 expansion I/O modules can be mounted on all slim type CPU modules. The maximum I/O points depend
on the CPU module type as described below.
The 20-I/O type CPU module (FC4A-D20K3 and FC4A-D20S3) can add a maximum of 128 I/O points, and use a maximum
of 148 points of inputs and outputs in total.
The 20-I/O relay output type CPU module (FC4A-D20RK1 and FC4A-D20RS1) can add a maximum of 224 I/O points, and
use a maximum of 244 points of inputs and outputs in total.
The 40-I/O type CPU module (FC4A-D40K3 and FC4A-D40S3) can add a maximum of 224 I/O points, and use a maximum
of 264 points of inputs and outputs in total.
Four models of the slim type CPU modules (FC4A-D20RK1, FC4A-D20RS1, FC4A-D40K3, and FC4A-D40S3) with system
program ver. 201 and higher can use the AS-Interface master module, and have additional internal relays and data regis-
ters for AS-Interface communication. Use WindLDR ver. 4.20 or higher to program the AS-Interface operands. For details
about AS-Interface communication, see a separate user's manual for the AS-Interface master module.
When the AS-Interface master module is not connected, these AS-Interface operands can be used for basic and advanced
instructions like ordinary internal relays and data registers. Note that these operands cannot be designated for keep or
clear operands in the Function Area Settings dialog box in
maintenance communication protocol and the designated reset input do not work on these AS-Interface operands. The sta-
tuses of these AS-Interface operands are maintained at power-up or when a reset input is turned on, but are cleared when
a keep data error occurs.
6-2
FC4A-D20K3
FC4A-D20S3
Allocation No.
Points
I0 - I7
12
I10 - I13
128
I30 - I187
(140 total)
Q0 - Q7
8
128
Q30 - Q187
(136 total)
M0 - M1277
1024
M8000 - M8157
128
R0 - R127
128
T0 - T99
100
C0 - C99
100
D0 - D1299
1300
D8000 - D8199
200
« FC4A M
FC4A-D20RK1
FC4A-D20RS1
Allocation No.
I0 - I7
I10 - I13
I30 - I307
Q0 - Q7
Q30 - Q307
M0 - M1277
M1300 - M1997
M8000 - M8157
R0 - R127
T0 - T99
C0 - C99
D0 - D1299
D1700 - D1999
D2000 - D7999
D8000 - D8199
WindLDR
. In addition, the clear operand data command of the
S
U
'
M
ICRO
MART
SER
S
ANUAL
FC4A-D40K3
FC4A-D40S3
Points
Allocation No.
I0 - I7
12
I10 - I17
I20 - I27
224
I30 - I307
(236 total)
Q0 - Q7
8
Q10 - Q17
224
Q30 - Q307
(232 total)
1024
M0 - M1277
560
M1300 - M1997
128
M8000 - M8157
128
R0 - R127
100
T0 - T99
100
C0 - C99
1300
D0 - D1299
300
D1700 - D1999
6000
D2000 - D7999
200
D8000 - D8199
»
Points
24
224
(248 total)
16
224
(240 total)
1024
560
128
128
100
100
1300
300
6000
200