Analog I/O Modules - IDEC FC4A-C10R2 User Manual

Fc4a series microsmart micro programmable logic controller
Table of Contents

Advertisement

Analog I/O Modules

Analog I/O modules are available in 3-I/O types, 2-, 4-, and 8-input types, and 1- and 2-output types. The input channel
can accept voltage and current signals, thermocouple and resistance thermometer signals, or thermistor signals. The output
channel generates voltage and current signals.
Analog I/O Module Type Numbers
Name
Analog I/O Module
Analog Input Module
Analog Output Module
END Refresh Type and Ladder Refresh Type
Depending on the internal circuit design for data refreshing, analog I/O modules are categorized into two types.
Analog I/O Module Category
Parameter Refreshing
While CPU
Analog I/O Data
is running
Refreshing
While CPU
Analog Output Data
is stopped
Refreshing
Data Register Allocation
END Refresh Type
Each END refresh type analog I/O module is allocated 20 data registers to store analog I/O data and parameters for con-
trolling analog I/O operation. These data registers are updated at every end processing while the CPU module is running.
WindLDR has ANST macro to program the analog I/O modules.
The CPU module checks the analog I/O configuration only once at the end processing in the first scan. If you have
changed the parameter while the CPU is running, stop and restart the CPU to enable the new parameter.
Ladder Refresh Type
Each ladder refresh type analog I/O module can be allocated any data registers to store analog I/O data and parameters
for controlling analog I/O operation. The data registers are programmed in the ANST macro. Analog I/O data are updated
at the ladder step following the ANST macro. Analog I/O parameters are updated when the ANST macro is executed, so
analog I/O parameters can be changed while the CPU is running.
I/O Signal
Voltage (0 to 10V DC)
Current (4 to 20mA)
Voltage (0 to 10V DC)
Current (4 to 20mA)
Thermocouple (K, J, T)
Resistance thermometer (Pt100)
Voltage (0 to 10V DC)
Current (4 to 20mA)
Voltage (0 to 10V DC)
Current (4 to 20mA)
Voltage (0 to 10V DC)
Current (4 to 20mA)
Thermocouple (K, J, T)
Resistance thermometer
(Pt100, Pt1000, Ni100, Ni1000)
Voltage (0 to 10V DC)
Current (4 to 20mA)
Thermistor (NTC, PTC)
Voltage (0 to 10V DC)
Current (4 to 20mA)
Voltage (–10 to +10V DC)
Current (4 to 20mA)
END Refresh Type
At the end processing in the first scan
At the end processing
When M8025 (maintain outputs while CPU
stopped) is on, output data is refreshed.
When off, output is turned off.
By default
« FC4A M
ICRO
I/O Points
2 inputs
1 output
2 inputs
1 output
2 inputs
4 inputs
8 inputs
8 inputs
1 output
2 outputs
When executing ANST macro
In the step after ANST macro
(always refreshed whether input to ANST is
on or off)
Maintains output status when the CPU is
stopped. Output data can be changed using
STPA instruction while the CPU is stopped.
See page 26-21.
Optionally designated in ANST macro
S
U
'
M
»
MART
SER
S
ANUAL
2: M
S
ODULE
PECIFICATIONS
Category
END Refresh Type
Ladder Refresh Type
END Refresh Type
Ladder Refresh Type
Ladder Refresh Type
Type No.
FC4A-L03A1
FC4A-L03AP1
FC4A-J2A1
FC4A-J4CN1
FC4A-J8C1
FC4A-J8AT1
FC4A-K1A1
FC4A-K2C1
2-43