Puls1 (Pulse Output 1); Puls2 (Pulse Output 2) - IDEC FC4A-C10R2 User Manual

Fc4a series microsmart micro programmable logic controller
Table of Contents

Advertisement

20: P
ULSE
Introduction
The PULS (pulse output) instruction is used to generate pulse outputs of 10 Hz through 20,000 Hz which can be used to
control pulse motors for simple position control applications.
The PWM (pulse width modulation) instruction is used to generate pulse outputs of 6.81, 27.26, or 217.86 Hz with a vari-
able pulse width ratio between 0% and 100%, which can be used for illumination control.
The RAMP instruction is used for trapezoidal control, and the ZRN instruction for zero-return control.
The PULS, PWM, and RAMP instructions can be used on all slim type CPU modules, and the ZRN instructions on the
FC4A-D20RK1, FC4A-D20RS1, FC4A-D40K3, and FC4A-D40S3 only.
Upgrade Information
Upgraded CPU modules have an additional option of operation mode 3 to select a frequency range from 10 Hz to 20 kHz
for the PULS and RAMP instructions, and also have special data registers D8055 and D8056 to store the current output
pulse frequency of the PULS and RAMP instructions. Applicable CPU modules and system program versions are shown
in the table below. For the procedure to confirm the system program version of the CPU module, see page 29-1.
CPU Module
System Program Version
Use
ver. 4.50 or higher to program the additional option for the PULS and RAMP instructions.
WindLDR

PULS1 (Pulse Output 1)

PULS
1
*****

PULS2 (Pulse Output 2)

PULS
2
*****
Note: The PULS1 and PULS2 instructions can be used only once in a user program. When PULS1 or PULS2 is not used,
unused output Q0 or Q1 can be used for another pulse instruction or ordinary output.
Applicable CPU Modules
FC4A-C10R2/C
FC4A-C16R2/C
I
NSTRUCTIONS
FC4A-C10R2
FC4A-C10R2C
When input is on, the PULS1 instruction sends out a pulse output from output
S1
D1
Q0. The output pulse frequency is determined by source operand S1. The output
*****
pulse width ratio is fixed at 50%.
PULS1 can be programmed to generate a predetermined number of output
pulses. When pulse counting is disabled, PULS1 generates output pulses while
the start input for the PULS1 instruction remains on.
When input is on, the PULS2 instruction sends out a pulse output from output
S1
D1
Q1. The output pulse frequency is determined by source operand S1. The output
*****
pulse width ratio is fixed at 50%.
PULS2 generates output pulses while the start input for the PULS2 instruction
remains on. PULS2 cannot be programmed to generate a predetermined number
of output pulses.
FC4A-C24R2/C
« FC4A M
All-in-One Type
FC4A-C16R2
FC4A-C24R2
FC4A-C16R2C
FC4A-C24R2C
FC4A-D20K3/S3
X
S
U
'
M
ICRO
MART
SER
S
ANUAL
Slim Type
FC4A-D20K3
FC4A-D20S3
204 or higher
FC4A-D20RK1/RS1 & FC4A-D40K3/S3
X
»
FC4A-D20RK1
FC4A-D20RS1
FC4A-D40K3
FC4A-D40S3
202 or higher
20-1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents