LOD (Load)
and LODN (Load Not)
The LOD instruction starts the logical operation with a NO (normally open) contact. The LODN instruction starts the log-
ical operation with a NC (normally closed) contact.
A total of eight LOD and/or LODN instructions can be programmed consecutively.
Ladder Diagram
OUT (Output)
The OUT instruction outputs the result of bit logical operation to the specified operand. The OUTN instruction outputs the
inverted result of bit logical operation to the specified operand.
Ladder Diagram
• For restrictions on ladder programming of OUT and OUTN instructions, see page 29-22.
Caution
Multiple OUT and OUTN
There is no limit to the number of OUT and OUTN instructions that can be programmed
into one rung.
Programming multiple outputs of the same output number is not recommended. How-
ever, when doing so, it is good practice to separate the outputs with the JMP/JEND set of
instructions, or the MCS/MCR set of instructions. These instructions are detailed later in
this chapter.
When the same output number is programmed more than once within one scan, the out-
put nearest to the END instruction is given priority for outputting. In the example on the
right, output Q0 is off.
7-2
Valid Operands
Instruction
I
LOD
0-307
LODN
The valid operand range depends on the CPU module type. For details, see pages 6-1 and 6-2.
and OUTN (Output Not)
Valid Operands
Instruction
I
OUT
OUTN
The valid operand range depends on the CPU module type. For details, see pages 6-1 and 6-2.
« FC4A M
Q
M
0-1277
0-307
8000-8157
Q
M
0-1277
0-307
8000-8077
S
U
'
M
ICRO
MART
SER
S
ANUAL
T
C
R
0-99
0-99
0-127
T
C
R
Ladder Diagram
I1
Ladder Diagram
ON
I1
OFF
I2
OFF
I3
»
I2
Q0
Q1
Q2
Q0
OFF
Q0
END