25: D Lc; Data Link System Setup - IDEC FC4A-C10R2 User Manual

Fc4a series microsmart micro programmable logic controller
Table of Contents

Advertisement

25: D
L
C
ATA
INK
OMMUNICATION

Data Link System Setup

To set up a data link system, install the RS485 communication adapter (FC4A-PC3) to the port 2 connector on the all-in-
one 16- or 24-I/O type CPU module.
When using the slim type CPU module, mount the RS485 communication module (FC4A-HPC3) next to the CPU module.
When using the optional HMI module with the slim type CPU module (not shown below), install the RS485 communica-
tion adapter (FC4A-PC3) to the port 2 connector on the HMI base module.
Connect the RS485 terminals A, B, and SG on every CPU module using a shielded twisted pair cable as shown below. The
total length of the cable for the data link system can be extended up to 200 meters (656 feet).
RS485 Communication
Adapter FC4A-PC3
on Port 2 Connector
RS485 Communication
Module FC4A-HPC3
Port 2
25-2
Master Station
A B SG
Cable
Slave Station 31
Shielded twisted pair cable 200 meters (656 feet) maximum
Core wire 0.3mm
« FC4A M
S
ICRO
MART
Slave Station 1
Slave Station 2
2
U
'
M
»
SER
S
ANUAL
All-in-One Type
CPU Module
A B SG
Cable
Slim Type
CPU Module

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents