IDEC FC4A-C10R2 User Manual page 51

Fc4a series microsmart micro programmable logic controller
Table of Contents

Advertisement

Relay Output Module Specifications
Type No.
Output Points and Common Lines
Terminal Arrangement
Maximum Load Current
Minimum Switching Load
Initial Contact Resistance
Electrical Life
Mechanical Life
Rated Load (resistive/inductive)
Dielectric Strength
Connector on Mother Board
Connector Insertion/Removal Durability
Internal Current Draw
Weight
Contact Protection Circuit for Relay Output
Note: When relay output modules are connected to the all-in-one 24-I/O type CPU module or any slim type CPU module, the
maximum number of relay outputs that can be turned on simultaneously, including the outputs on the CPU module, are
shown below.
CPU Module Type
Maximum Relay Outputs Turning On Simultaneously
Output Delay
Output Relay Status
All Outputs ON
All Outputs OFF
ON
Command
OFF
ON
OFF
« FC4A M
FC4A-R081
8 NO contacts in 2 common lines
See Relay Output Module Terminal Arrangement on page 2-32.
2A per point
7A per common line
0.1 mA/0.1V DC (reference value)
30 mΩ maximum
100,000 operations minimum (rated load 1,800 operations/hour)
20,000,000 operations minimum (no load 18,000 operations/hour)
240V AC/2A, 30V DC/2A
Between output and
or
Between output terminal and internal circuit: 1,500V AC, 1 minute
Between output terminals (COMs):
MC1.5/11-G-3.81BK
(Phoenix Contact)
100 times minimum
30 mA (5V DC)
40 mA (24V DC)
5 mA (5V DC)
0 mA (24V DC)
110g
See page 3-15.
All-in-One 24-I/O CPU Module
OFF delay:
Chatter:
ON delay:
S
U
'
M
ICRO
MART
SER
S
ANUAL
2: M
ODULE
FC4A-R161
16 NO contacts in 2 common lines
8A per common line
terminals:
1,500V AC, 1 minute
1,500V AC, 1 minute
MC1.5/10-G-3.81BK
(Phoenix Contact)
100 times minimum
45 mA (5V DC)
75 mA (24V DC)
5 mA (5V DC)
0 mA (24V DC)
145g
Slim Type CPU Module
33
10 ms maximum
6 ms maximum
6 ms maximum
»
S
PECIFICATIONS
54
2-31

Hide quick links:

Advertisement

Table of Contents
loading