CUD (Up/Down Selection Reversible Counter)
The up/down selection reversible counter CUD has a selection input to switch the up/down gate, so that three inputs are
required. The circuit for an up/down selection reversible counter must be programmed in the following order: preset input,
pulse input, up/down selection input, the CUD instruction, and a counter number C0 through C99, followed by a counter
preset value from 0 to 65535.
The preset value can be designated using a decimal constant or a data register. When a data register is used, the data of the
data register becomes the preset value.
Ladder Diagram
Preset Input
CUD
C2
500
I0
Pulse Input
I1
U/D Selection
I2
I3
C2
Q2
Timing Chart
ON
Preset Input I0
OFF
ON
Pulse Input I1
OFF
U/D Selection
ON
Input I2
OFF
500 501 502 501
Counter C2 Value
ON
Counter C2
OFF
Valid Pulse Inputs
The reset or preset input has priority over the pulse input.
One scan after the reset or preset input has changed from on
to off, the counter starts counting the pulse inputs as they
change from off to on.
ON
Reset/Preset
OFF
ON
Pulse
OFF
More than one scan
time is required.
• For restrictions on ladder programming
Caution
of counter instructions, see page 29-22.
7-12
Program List
Instruction
Data
LOD
I0
LOD
I1
LOD
I2
CUD
C2
500
LOD
I3
AND
C2
OUT
Q2
• • •
• • •
500 499
0
1
500 500
Valid
Invalid
Valid
« FC4A M
S
ICRO
MART
• The same counter number cannot be pro-
grammed more than once.
• The preset input must be turned on initially so
that the current value returns to the preset
value.
• The preset input must be turned off before
counting may begin.
• The up mode is selected when the up/down
selection input is on.
• The down mode is selected when the up/
down selection input is off.
• The counter output is on only when the cur-
rent value is 0.
• After the current value reaches 0 (counting
down), it changes to 65535 on the next count
down.
• After the current value reaches 65535 (count-
ing up), it changes to 0 on the next count up.
• When power is off, the counter's current
value is held, and can also be designated as
"clear" type counters using the Function Area
Settings (see page 5-4).
• Counter preset and current values can be
changed using
ing the entire program to the CPU again.
From the
WindLDR
Monitor, then select Online > Point Write.
To change a counter preset value, specify the
counter number with a capital C and a new
preset value. To change a counter current
value, specify the counter number with a
small c and a new current value while the
counter preset input is off.
• When the preset or current value is changed
during counter operation, the change
becomes effective immediately.
• For the data movement when changing, con-
firming, and clearing preset values, see page
7-13. Preset values can also be changed and
changed preset values can be confirmed using
the HMI module. See pages 5-35 and 5-36.
U
'
M
»
SER
S
ANUAL
WindLDR
without download-
menu bar, select Online >

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents