0020h: User Program RAM Sum Check Error
The data of the user program compile area in the
user program is recompiled automatically, and the timer/counter preset values and expansion data register preset values are
initialized to the values of the user program. Note that changed preset values are cleared and that the original values are
restored. Clear the error code using the HMI module or
0040h: Keep Data Error
This error indicates that the data designated to be maintained during power failure is broken because of memory backup
failure. Note that the "keep" data of internal relays and shift registers are cleared. Data of counters and data registers are
also cleared. Clear the error code using the HMI module or
If this error occurs in a short period of power interruption after the battery has been charged as specified, the battery is
defective and the CPU module has to be replaced.
0080h: User Program Syntax Error
This error indicates that the user program has a syntax error. Correct the user program, and download the corrected user
program to the
MicroSmart
0100h: User Program Writing Error
This error indicates a failure of writing into the
The error code is cleared when writing into the EEPROM is completed successfully. If this error occurs frequently, the
CPU module has to be replaced.
MicroSmart
When a memory cartridge is installed on the CPU module, writing into the memory cartridge is checked.
0200h: CPU Module Error
This error is issued when the EEPROM is not found. When this error occurred, turn power off and on. Clear the error code
using the HMI module or
replaced.
0400h: Clock IC Error
This error indicates that the real time calendar/clock in the clock cartridge has lost clock backup data or has an error
caused by invalid clock data.
Clear the error code and set the calendar/clock data using the HMI module or
will recover from the error. If the error continues, the clock cartridge has to be replaced. See Troubleshooting Diagram on
page 29-21.
2000h: I/O Bus Initialize Error
This error indicates that an I/O module has a fault. If this error occurs frequently or normal I/O function is not restored
automatically, the I/O module has to be replaced.
MicroSmart
. The error code is cleared when a correct user program is transferred.
MicroSmart
on a computer. If this error occurs frequently, the
WindLDR
« FC4A M
CPU module RAM is broken.When this error occurs, the
on a computer.
WindLDR
on a computer.
WindLDR
CPU module EEPROM when downloading a user program.
S
U
'
M
ICRO
MART
SER
S
ANUAL
29: T
ROUBLESHOOTING
CPU module has to be
MicroSmart
on a computer. The clock cartridge
WindLDR
»
29-5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents