Communication Adapters And Communication Modules - IDEC FC4A-C10R2 User Manual

Fc4a series microsmart micro programmable logic controller
Table of Contents

Advertisement

Communication Adapters and Communication Modules

All
CPU modules have communication port 1 for RS232C communication. In addition, all-in-one 16- and 24-
MicroSmart
I/O type CPU modules have a port 2 connector. An optional communication adapter can be installed on the port 2 connec-
tor for RS232C or RS485 communication. The 10-I/O type CPU module does not have a port 2 connector.
A communication module can be attached to any slim type CPU module to use port 2 for additional RS232C or RS485
communication. When the HMI base module is attached to a slim type CPU module, a communication adapter can be
installed to the port 2 connector on the HMI base module.
When using the RS232C communication adapter or communication module for port 2, maintenance communication, user
communication, and modem communication are made possible. With the RS485 communication adapter or communica-
tion module installed, maintenance communication, data link communication, and user communication (upgraded CPU
modules of slim 20-I/O relay output types and 40-I/O types only) can be used on port 2.
Communication Adapter and Communication Module Type Numbers
Name
RS232C Communication Adapter
RS485 Communication Adapter
RS232C Communication Module
RS485 Communication Module
Parts Description
RS232C Communication Adapter (Mini DIN)
RS485 Communication Adapter (Mini DIN)
(1) Port 2
(2) Connector
RS232C Communication Module (Mini DIN)
RS485 Communication Module (Mini DIN)
(3) Hinged Lid
(1) Communication Connector
(2) Port 2
(3) Hinged Lid
Mini DIN connector
Mini DIN connector
Screw Terminal Block
Mini DIN connector
Mini DIN connector
Screw Terminal Block
(1) Port 2
(2) Connector
RS232C or RS485 communication port 2.
Connects to the port 2 connector on the all-in-one type CPU module or HMI base module.
(1) Communication
Connector
(2) Port 2
Connects to the slim type CPU module.
RS232C or RS485 communication port 2.
Open the lid to gain access to port 2.
« FC4A M
S
ICRO
Termination
RS485 Communication Adapter (Screw Terminal)
RS485 Communication Module (Screw Terminal)
(3) Hinged Lid
U
'
M
»
MART
SER
S
ANUAL
2: M
S
ODULE
PECIFICATIONS
Type No.
FC4A-PC1
FC4A-PC2
FC4A-PC3
FC4A-HPC1
FC4A-HPC2
FC4A-HPC3
(1) Port 2
(2) Connector
(1) Communication
Connector
(2) Port 2
2-61

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents