IDEC FC4A-C10R2 User Manual page 139

Fc4a series microsmart micro programmable logic controller
Table of Contents

Advertisement

Catching Rising Edge of Input Pulse
Actual Input
ON
(I2 to I5)
OFF
Catch Input Relay
ON
(M8154-M8157)
OFF
END
Processed
Catching Falling Edge of Input Pulse
Actual Input
ON
(I2 to I5)
OFF
Catch Input Relay
ON
(M8154-M8157)
OFF
END
Processed
Note: When two or more pulses enter within one scan, subsequent pulses are ignored.
Example: Maintaining Catch Input
When a catch input is received, the catch input relay assigned to a catch input is turned on for only one scan. This example
demonstrates a program to maintain a catch input status for more than one scan.
M8154
I1
M0
M0
M0
1 scan time
1 scan time
Input I2 is designated as a catch input using the Function Area Settings.
When input I2 is turned on, special internal relay M8154 is turned on, and M0 is maintained
in the self-holding circuit.
When NC input I1 is turned off, the self-holding circuit is unlatched, and M0 is turned off.
M0 is used as an input condition for the subsequent program instructions.