Catching Rising Edge of Input Pulse
Actual Input
ON
(I2 to I5)
OFF
Catch Input Relay
ON
(M8154-M8157)
OFF
END
Processed
Catching Falling Edge of Input Pulse
Actual Input
ON
(I2 to I5)
OFF
Catch Input Relay
ON
(M8154-M8157)
OFF
END
Processed
Note: When two or more pulses enter within one scan, subsequent pulses are ignored.
Example: Maintaining Catch Input
When a catch input is received, the catch input relay assigned to a catch input is turned on for only one scan. This example
demonstrates a program to maintain a catch input status for more than one scan.
M8154
I1
M0
M0
M0
1 scan time
1 scan time
Input I2 is designated as a catch input using the Function Area Settings.
When input I2 is turned on, special internal relay M8154 is turned on, and M0 is maintained
in the self-holding circuit.
When NC input I1 is turned off, the self-holding circuit is unlatched, and M0 is turned off.
M0 is used as an input condition for the subsequent program instructions.
« FC4A M
ICRO
S
U
'
M
»
MART
SER
S
ANUAL
5: S
PECIAL
Note
Note
F
UNCTIONS
5-19