Troubles at System Start-up
The following table summarizes possible troubles at system start-up, probable causes and actions to be taken.
Trouble
PWR LED is off.
(power)
FLT LED is on.
(fault)
LMO LED is on.
(local mode)
OFF LED is on.
(offline)
Slave operation is unstable.
AS-Interface power is not supplied to the AS-Interface master module. Check that
wiring is correct and AS-Interface power is supplied.
Power is not supplied from the CPU module to the AS-Interface master module.
Check the connection between the CPU module and the AS-Interface master module.
Slave configuration on the bus is incorrect. Use the WindLDR slave monitor function
to check that slaves are connected correctly. Perform configuration, if necessary. For
the configuration method, see page 28-30.
If FLT LED remains on even though slaves are connected correctly and configuration is
completed, either disconnect and reconnect the AS-Interface connector, or turn off and
on the AS-Interface power supply.
The CPU module fails to communicate with the AS-Interface master module. Check the
following points.
Is the CPU module compatible with AS-Interface? Check the Type No. of the CPU
module.
Is a check mark put in the check box "Use AS-Interface Master Module" in WindLDR
Function Area Settings? The box is checked as default. If not, put a check mark and
download the user program to the CPU module.
While a slave of address 0 was connected, power was turned on. After changing the
slave address, power up again. For the address changing method, see page 28-31.
Check if there are two or more slaves with the same address. Each slave must have
a unique address. If two slaves have the same address and same identification
codes (ID, I/O, ID2, ID1), the AS-Interface master module may fail to detect an error.
When changing the duplicate slave address using WindLDR, remove one of the
slaves from the bus.