Operand Allocation Numbers - IDEC FC4A-C10R2 User Manual

Fc4a series microsmart micro programmable logic controller
Table of Contents

Advertisement

6: A
LLOCATION
Introduction
This chapter describes allocation numbers available for the
cial internal relays and special data registers are also described.
The
is programmed using operands such as inputs, outputs, internal relays, timers, counters, shift registers,
MicroSmart
and data registers.
Inputs (I) are relays to receive input signals through the input terminals.
Outputs (Q) are relays to send the processed results of the user program to the output terminals.
Internal relays (M) are relays used in the CPU and cannot be outputted to the output terminals.
Special internal relays (M) are internal relays dedicated to specific functions.
Timers (T) are relays used in the user program, available in 1-sec, 100-ms, 10-ms, and 1-ms timers.
Counters (C) are relays used in the user program, available in adding counters and reversible counters.
Shift registers (R) are registers to shift the data bits according to pulse inputs.
Data registers (D) are registers used to store numerical data. Some of the data registers are dedicated to special functions.

Operand Allocation Numbers

Available I/O numbers depend on the type of the
ules can be used with only the 24-I/O type CPU module among all-in-one type CPU modules. All slim type CPU modules
can be used with I/O modules to expand the I/O points. For details of I/O, internal relay, and special internal relay num-
bers, see page 6-3.
All-in-One Type CPU Modules
Operand
Input (I)
Expansion Input (I)
Output (Q)
Expansion Output (Q)
Internal Relay (M)
Special Internal
Relay (M)
Shift Register (R)
Timer (T)
Counter (C)
Data Register (D)
Special Data
Register (D)
Notes:
The least significant digit of input, output, internal relay, and special internal relay operand number is an octal number (0
through 7). Upper digits are decimal numbers.
The allocation numbers of expansion inputs and outputs start with I30 and Q30, respectively.
Note that input and output allocation numbers are not continuous between the CPU module and expansion I/O modules.
The 24-I/O type CPU module (FC4A-C24R2 and FC4A-C24R2C) can add a maximum of 64 I/O points, and use a maximum
of 88 points of inputs and outputs in total.
N
UMBERS
MicroSmart
FC4A-C10R2
FC4A-C10R2C
Allocation No.
Points
I0 - I5
6
Q0 - Q3
4
M0 - M317
256
M8000 - M8157
128
R0 - R63
64
T0 - T31
32
C0 - C31
32
D0 - D399
400
D8000 - D8099
100
« FC4A M
to program basic and advanced instructions. Spe-
MicroSmart
CPU module and the combination of I/O modules. I/O mod-
FC4A-C16R2
FC4A-C16R2C
Allocation No.
Points
I0 - I7
9
I10
Q0 - Q6
7
M0 - M1277
1024
M8000 - M8157
128
R0 - R127
128
T0 - T99
100
C0 - C99
100
D0 - D1299
1300
D8000 - D8199
200
S
U
'
M
ICRO
MART
SER
S
ANUAL
FC4A-C24R2
FC4A-C24R2C
Allocation No.
I0 - I7
I10 - I15
I30 - I107
Q0 - Q7
Q10 - Q11
Q30 - Q107
M0 - M1277
M8000 - M8157
R0 - R127
T0 - T99
C0 - C99
D0 - D1299
D8000 - D8199
»
Points
14
64 (78 total)
10
64 (74 total)
1024
128
128
100
100
1300
200
6-1