FC4A-J2A1 (Analog Input Module) — Screw Terminal Type
Applicable Terminal Block:
FC4A-J4CN1 (Analog Input Module) — Screw Terminal Type
Applicable Terminal Block:
•
Connect a fuse appropriate for the applied voltage and current draw, at the position shown in the diagram. This is
required when equipment containing the MicroSmart is destined for Europe.
•
When connecting a resistance thermometer, connect three wires B, B', and A to the CS (current sense), +, and – termi-
nals of input channels IN0 through IN3, respectively.
•
When connecting a thermocouple, connect the + wire to the + terminal and the – wire to the CS and – terminals.
•
Do not connect the thermocouple to a hazardous voltage (60V DC or 42.4V peak or higher).
•
Do not connect any wiring to unused terminals.
•
– terminals of input channels IN0 through IN3 are interconnected.
2-52
FC4A-PMT11P (supplied with the analog input module)
•
Connect a fuse appropriate for the applied voltage and current draw, at the position shown in the
diagram. This is required when equipment containing the MicroSmart is destined for Europe.
•
Do not connect any wiring to unused terminals.
FC4A-PMT10P (supplied with the analog input module)
« FC4A M
24V DC
–
+
Analog voltage/current
output device
Analog voltage/current
output device
24V DC
–
+
Analog voltage
output device
Analog current
output device
Resistance
thermometer
+
Thermocouple
–
S
U
'
M
ICRO
MART
SER
S
ANUAL
Terminal No.
Fuse
+
–
NC
NC
NC
+
+
–
–
NC
+
+
–
–
Fuse
Terminal No.
24V
0V
NC
CS
+
+
–
–
I–
NC
CS
+
+
–
–
I–
B
CS
B'
+
A
–
I–
NC
CS
+
–
I–
NC
»
Channel
24V DC
—
IN0
IN1
Channel
24V DC
—
IN0
IN1
IN1
IN2
IN3