This section describes simple operating procedures for the basic AS-Interface system from programming
computer to monitoring the slave operation.
AS-Interface System Setup
The sample AS-Interface system consists of the following devices:
Name
FC4A MicroSmart Slim Type CPU Module
MicroSmart AS-Interface Master Module
WindLDR
AS-Interface Standard Slave
AS-Interface Power Supply
AS-Interface Cable Wiring
Before wiring the AS-Interface cable, remove the AS-Interface cable terminal block from the AS-Interface cable connector
on the AS-Interface master module.
AS-Interface specifies use of brown cables for the AS-Interface + line, and blue cables for the AS-Interface – line. Connect
the cables to match the color labels on the terminal block. Tighten the terminal screws to a torque of 0.5 to 0.6 N·m.
Insert the terminal block to the connector on the AS-Interface master module, and tighten the mounting screws to a torque
of 0.3 to 0.5 N·m.
Brown AS-Interface +
Blue AS-Interface –
28-6
C
ASTER
OMMUNICATION
Computer Link Cable 4C
FC2A-KC4C
3m (9.84 ft.) long
Use a ferrule.
Use a ferrule.
« FC4A M
Type No.
FC4A-D20RK1
FC4A-AS62M
FC9Y-LP2CDW
PS2R-Q30ABL
Slim Type CPU Module
FC4A-D20RK1
AS-Interface Power Supply
Standard Slave
Address 0
ID: 0, I/O: 7, ID2: F, ID1: 7
Brown Label
Blue Label
S
U
'
M
ICRO
MART
SER
S
ANUAL
Description
Version 5.0 or higher
1 unit
Address 0
ID: 0, I/O: 7, ID2: F, ID1: 7
Output 30.5V DC, 2.4A (73W)
AS-Interface Master Module
FC4A-AS62M
»
on a
WindLDR
Standard
AS-Interface Cable

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents