Relay Output Specifications (All-in-One Type CPU Module)
CPU Module
No. of Outputs
Output Points per Common Line
Terminal Arrangement
Maximum Load Current
Minimum Switching Load
Initial Contact Resistance
Electrical Life
Mechanical Life
Rated Load (resistive/inductive)
Dielectric Strength
Contact Protection Circuit for Relay Output
Output Delay
Output Relay Status
COM0
COM1
COM2
COM3
ON
Command
OFF
ON
OFF
« FC4A M
FC4A-C10R2
FC4A-C10R2C
4 points
7 points
3 NO contacts
4 NO contacts
1 NO contact
2 NO contacts
—
1 NO contact
—
—
See CPU Module Terminal Arrangement on pages 2-8 and 2-9.
2A per point
8A per common line
0.1 mA/0.1V DC (reference value)
30 mΩ maximum
100,000 operations minimum (rated load 1,800 operations/hour)
20,000,000 operations minimum (no load 18,000 operations/hour)
240V AC/2A, 30V DC/2A
Between output and
or
Between output terminal and internal circuit: 1,500V AC, 1 minute
Between output terminals (COMs):
See page 3-15.
OFF delay:
Chatter:
ON delay:
S
U
'
M
ICRO
MART
SER
S
ANUAL
2: M
ODULE
FC4A-C16R2
FC4A-C16R2C
10 points
4 NO contacts
4 NO contacts
1 NO contact
1 NO contact
terminals:
1,500V AC, 1 minute
1,500V AC, 1 minute
10 ms maximum
6 ms maximum
6 ms maximum
»
S
PECIFICATIONS
FC4A-C24R2
FC4A-C24R2C
2-7