IDEC FC4A-C10R2 User Manual page 23

Fc4a series microsmart micro programmable logic controller
Table of Contents

Advertisement

General Specifications (All-in-One Type CPU Module)
Normal Operating Conditions
AC Power Type
CPU Module
DC Power Type
Operating Temperature
Storage Temperature
Relative Humidity
Pollution Degree
Degree of Protection
Corrosion Immunity
Altitude
Vibration Resistance
Shock Resistance
ESD Immunity
AC Power Type
Weight
DC Power Type
Power Supply
Rated Power Voltage
Allowable Voltage Range
Rated Power Frequency
Maximum Input Current
AC Power Type
Maximum
Power
Consumption
DC Power Type
Allowable Momentary Power
Interruption
Dielectric Strength
Insulation Resistance
Noise Resistance
Inrush Current
Grounding Wire
Power Supply Wire
Effect of Improper Power
Supply Connection
Note: The maximum number of relay outputs that can be turned on simultaneously is 33 points (AC power type CPU module)
or 44 points (DC power type CPU module) including relay outputs on the CPU module.
FC4A-C10R2
FC4A-C10R2C
0 to 55°C (operating ambient temperature)
–25 to +70°C
10 to 95% (non-condensing)
2 (IEC 60664-1)
IP20 (IEC 60529)
Atmosphere free from corrosive gases
Operation: 0 to 2,000m (0 to 6,565 feet)
Transport: 0 to 3,000m (0 to 9,840 feet)
When mounted on a DIN rail or panel surface:
5 to 9 Hz amplitude 3.5 mm, 9 to 150 Hz acceleration 9.8 m/s
2 hours per axis on each of three mutually perpendicular axes (IEC 61131-2)
2
147 m/s
(15G), 11 ms duration, 3 shocks per axis on three mutually perpendicular
axes (IEC 61131-2)
Contact discharge: ±6 kV, Air discharge: ±8 kV (IEC 61000-4-2)
230g
240g
AC power type: 100 to 240V AC, DC power type: 24V DC
AC power type: 85 to 264V AC, DC power type: 20.4 to 28.8V DC (including ripple)
AC power type: 50/60 Hz (47 to 63 Hz)
250 mA (85V AC)
160 mA (24V DC)
FC4A-C10R2: 30VA (264V AC), 20VA (100V AC) (CPU module*)
FC4A-C16R2: 31VA (264V AC), 22VA (100V AC) (CPU module*)
FC4A-C24R2: 40VA (264V AC), 33VA (100V AC) (CPU module* + 4 I/O modules)
*The CPU module power consumption includes 250mA sensor power.
FC4A-C10R2C: 3.9W (24V DC) (CPU module)
FC4A-C16R2C: 4.6W (24V DC) (CPU module)
FC4A-C24R2C: 8.7W (24V DC) (CPU module + 4 I/O modules)
10 ms (at the rated power voltage)
Between power and
or
Between I/O and
or
Between power and
or
Between I/O and
or
AC or DC power terminals:
I/O terminals (coupling clamp):
35A maximum
UL1007 AWG16
UL1015 AWG22, UL1007 AWG18
Reverse polarity:
Improper voltage or frequency: Permanent damage may be caused
Improper lead connection:
« FC4A M
S
ICRO
MART
FC4A-C16R2
FC4A-C16R2C
250g
260g
300 mA (85V AC)
190 mA (24V DC)
terminals:
1,500V AC, 1 minute
terminals:
1,500V AC, 1 minute
terminals:
10 MΩ minimum (500V DC megger)
terminals:
10 MΩ minimum (500V DC megger)
1.5 kV, 50 nsec to 1 µs
1.5 kV, 50 nsec to 1 µs
35A maximum
Normal operation (AC), No operation, no damage (DC)
Permanent damage may be caused
U
'
M
»
SER
S
ANUAL
2: M
S
ODULE
PECIFICATIONS
FC4A-C24R2
FC4A-C24R2C
2
(1G)
305g
310g
450 mA (85V AC)
360 mA (24V DC)
40A maximum
2-3

Hide quick links: