IDEC FC4A-C10R2 User Manual page 60

Fc4a series microsmart micro programmable logic controller
Table of Contents

Advertisement

2: M
S
ODULE
PECIFICATIONS
Mixed I/O Module Specifications
Type No.
I/O Points
Terminal Arrangement
Connector on Mother Board
Connector Insertion/Removal Durability
Internal Current Draw
Weight
DC Input Specifications (Mixed I/O Module)
Input Points and Common Line
Rated Input Voltage
Input Voltage Range
Rated Input Current
Input Impedance
Turn ON Time
Turn OFF Time
Isolation
External Load for I/O Interconnection
Signal Determination Method
Effect of Improper Input Connection
Cable Length
Input Operating Range
The input operating range of the Type 1 (IEC 61131-2)
input module is shown below:
28.8
24
15
5
0
1.2
Input Current (mA)
Input Internal Circuit
3.3 kΩ
Input
COM
2-40
4 inputs in 1 common line
4 outputs in 1 common line
See Mixed I/O Module Terminal Arrangement on pages 2-41 and 2-42.
MC1.5/11-G-3.81BK
(Phoenix Contact)
100 times minimum
25 mA (5V DC)
All I/Os ON
20 mA (24V DC)
5 mA (5V DC)
All I/Os OFF
0 mA (24V DC)
95g
4 points in 1 common line
24V DC sink/source input signal
20.4 to 28.8V DC
7 mA/point (24V DC)
3.4 kΩ
4 ms (24V DC)
4 ms (24V DC)
Between input terminals:
Internal circuit:
Not needed
Static
Both sinking and sourcing input signals can be connected. If any input
exceeding the rated value is applied, permanent damage may be caused.
3m (9.84 ft.) in compliance with electromagnetic immunity
ON Area
Transition
Area
OFF Area
4.2
7
8.4
« FC4A M
FC4A-M08BR1
Not isolated
Photocoupler isolated
I/O Usage Limits
When using the FC4A-M24BR2 at an ambient tempera-
ture of 55°C in the normal mounting direction, limit the
inputs and outputs, respectively, which turn on simulta-
neously along line (1).
When using at 45°C, all I/Os can be turned on simulta-
neously at input voltage 28.8V DC as indicated with line
(2).
When using the FC4A-M08BR1, all I/Os can be turned on
simultaneously at 55°C, input voltage 28.8V DC.
S
U
'
M
ICRO
MART
SER
S
ANUAL
FC4A-M24BR2
16 inputs in 1 common line
8 outputs in 2 common lines
Input:
F6018-17P (Fujicon)
Output: F6018-11P (Fujicon)
Not removable
65 mA (5V DC)
45 mA (24V DC)
10 mA (5V DC)
0 mA (24V DC)
140g
16 points in 1 common line
(2) 45°C
28.8
26.4
(1) 55°C
0
0
80
I/O Simultaneous ON Ratio (%)
»
100

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents