CDP (Dual-Pulse Reversible Counter)
The dual-pulse reversible counter CDP has up and down pulse inputs, so that three inputs are required. The circuit for a
dual-pulse reversible counter must be programmed in the following order: preset input, up-pulse input, down-pulse input,
the CDP instruction, and a counter number C0 through C99, followed by a counter preset value from 0 to 65535.
The preset value can be designated using a decimal constant or a data register. When a data register is used, the data of the
data register becomes the preset value.
Ladder Diagram
Preset Input
CDP
C1
500
I0
Up Pulse
I1
Down Pulse
I2
I3
C1
Q1
Timing Chart
ON
Preset Input I0
OFF
ON
Up Pulse I1
OFF
ON
Down Pulse I2
OFF
500 501 502 501
Counter C1 Value
ON
Counter C1
OFF
• For restrictions on ladder programming
Caution
of counter instructions, see page 29-22.
Program List
Instruction
Data
LOD
I0
LOD
I1
LOD
I2
CDP
C1
500
LOD
I3
AND
C1
OUT
Q1
• • •
• • •
500 499
0
1
500 500
« FC4A M
S
ICRO
MART
• The same counter number cannot be pro-
grammed more than once.
• The preset input must be turned on initially so
that the current value returns to the preset
value.
• The preset input must be turned off before
counting may begin.
• When the up pulse and down pulses are on
simultaneously, no pulse is counted.
• The counter output is on only when the cur-
rent value is 0.
• After the current value reaches 0 (counting
down), it changes to 65535 on the next count
down.
• After the current value reaches 65535 (count-
ing up), it changes to 0 on the next count up.
• When power is off, the counter's current
value is held, and can also be designated as
"clear" type counters using the Function Area
Settings (see page 5-4).
• Counter preset and current values can be
changed using
ing the entire program to the CPU again.
From the
WindLDR
Monitor, then select Online > Point Write.
To change a counter preset value, specify the
counter number with a capital C and a new
preset value. To change a counter current
value, specify the counter number with a
small c and a new current value while the
counter preset input is off.
• When the preset or current value is changed
during counter operation, the change
becomes effective immediately.
• For the data movement when changing, con-
firming, and clearing preset values, see page
7-13. Preset values can also be changed and
changed preset values can be confirmed using
the HMI module. See pages 5-35 and 5-36.
U
'
M
»
SER
S
ANUAL
7: B
I
ASIC
NSTRUCTIONS
without download-
WindLDR
menu bar, select Online >
7-11