Error Code List - Mitsubishi Electric MELSEC iQ-R Series User Manual

System recorder
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error code list

The following table shows the error code list of a recorder module.
Error code
Error name
*1
0C00H
Recording Start with Program
Inconsistency
*1
0C01H
Program Inconsistency during
Recording Operation
1300H
Co-recording setting error
1301H
Co-recording setting error
1810H
Recording Setting Acquisition
Error
1811H to 1813H
Recording Setting Error
1814H
Recording Start Error in Sub
1815H
Recording Start Error in Sub
1816H
Module Error
1817H
Recording Setting Error
1818H
Co-recording unsupported sub
error
1830H
Recording Setting Error
1850H
Recording Setting Error
1851H
Recording Setting Error
1900H
Recording Files Saving Error
5 TROUBLESHOOTING
168
5.6 Recorder Module
Error description
It is different from the project (program, FB/
FUN) at the recording setting because a
program file or FB/FUN file in the CPU
module was changed during recording
operation.
When a device/label that is not a sampling
target is added, the added device/label
cannot be saved and replayed.
It is different from the project (program, FB/
FUN) at the recording setting because a
program file or FB/FUN file in the CPU
module was changed during recording
operation.
When a device/label that is not a sampling
target is added, the added device/label
cannot be saved and replayed.
The co-recording function does not operate
because it is not supported by the firmware
version of the CPU module.
The co-recording function does not operate
because the co-recording setting of the CPU
module is not set to "Use".
Failed to acquire the recording setting.
The contents of the recording setting file are
broken.
A recording start error has occurred in the
Sub.
• The mode of the module parameter is not
set to "Online" in some Sub.
• The module status setting is set to
"Empty" with the system parameter (I/O
assignment setting) in some Sub.
• The Sub is not mounted.
An unrecognized error has been detected by
the firmware version of the target recorder
module.
The contents of the recording setting file are
broken.
The sub version not supported by the co-
recording function is provided.
A recording setting file which is not
supported by the firmware version of the
target recorder module was written.
The size is not set in the buffer area for data
sampling of the CPU parameter.
The size is not set in the recording buffer of
the basic settings of the module parameter.
Failed to save recording files because there
is no free folder number for recording
folders.
Corrective action
When a device/label that is not a sampling target is
added, stop recording, write the recording setting file to
the CPU module again, and restart recording.
When the devices/labels in the program are not
specified in a batch in the device/label sampling target
setting, please review the recording setting so that the
added devices/labels are included in the sampling
targets and write it to the CPU module.
When a device/label that is not a sampling target is
added, stop recording, write the recording setting file to
the CPU module again, and restart recording.
When the devices/labels in the program are not
specified in a batch in the device/label sampling target
setting, please review the recording setting so that the
added devices/labels are included in the sampling
targets and write it to the CPU module.
Please check the version of the CPU module, use a
compatible product, and then write the CPU parameter
again.
Please set the co-recording setting of the CPU
parameter to "Use".
Please write the recording setting with the engineering
tool.
• Please write the recording setting again with the
engineering tool.
• Please check that the versions of the recorder
module, CPU module, and engineering tool are
appropriate to be used together.
Please check the details of the Sub error by the module
diagnostics of the engineering tool, and clear the error.
• Please set the operation mode of the module
parameter of the Sub whose recording function is to
be used to "Online".
• Please set the module status setting of the system
parameter (I/O assignment setting) of the Sub whose
recording function is to be used to "No setting".
• Please check the system parameter and actual
system configuration, please review the recording
setting.
Please check that the versions of the recorder module,
CPU module, and engineering tool are appropriate to
be used together.
• Please write the recording setting again with the
engineering tool.
• Please check that the versions of the recorder
module, CPU module, and engineering tool are
appropriate to be used together.
Please check the sub version and use a product
supported by the co-recording function.
Please check the version of the recorder module, use a
compatible product, and then write the recording file
again.
Please set the size in the buffer area for data sampling
of the CPU parameter.
Please set the size in the recording buffer of the basic
settings of the module parameter.
Please delete unnecessary recording folders in the
setting-specific folder in which the error has occurred.