Error code

Error code
Description
100H
The setting value of i_udJsonAddr (JSON start address) exceeds
the maximum value of file register.
101H
The setting value of uType (type of Value) of pb_st30Member
(member list) is out of range.
A value other than 0 to 4 is set for the type of Value.
102H
The setting value of uDepth (depth of hierarchy) of pb_st30Member
(member list) is out of range.
A value other than 1 to 30 is set for the depth of hierarchy.
103H
The number of characters in s32Key (Key string) of
pb_st30Member (member list) is out of range.
Unintended memory in the CPU may be accessed.
200H
i_bEN (execution command) is turned off during processing.
201H
A JSON string that is not available in this FB is stored.
202H
The number of members of JSON string exceeds 30.
*1 Output only for one scan.
Action
Check and correct the setting, then execute the FB again.
Check and correct the setting, then execute the FB again.
Check and correct the setting, then execute the FB again.
Set s32Key (Key string) using 31 characters or less.
i_bEN (execution command) must be on until normal completion or
error completion turns on.
Correct the target JSON string, then execute the FB again.
Correct the target JSON string, then execute the FB again.