Setting the Rotation Detection Level
Use the following parameter to set the speed detection level at which to output the /TGON sig-
nal.
• Rotary Servomotors
Rotation Detection Level
Setting Range
Pn502
1 to 10,000
• Linear Servomotors
Zero Speed Level
Pn581
Setting Range
1 to 10,000
6.1.7

/S-RDY (Servo Ready) Signal

The /S-RDY (Servo Ready) signal turns ON when the SERVOPACK is ready to accept the /S-
ON (Servo ON) input signal.
The /S-RDY signal is turned ON under the following conditions.
• Main circuit power supply is ON.
• There is no hard wire base block state.
• There are no alarms.
• If an absolute encoder is used, the SEN (Absolute Data Request) signal is ON (high level).
• If a Servomotor without a polarity sensor is used, polarity detection has been completed.
• If an absolute encoder is used, the SERVOPACK must be ready to accept the /S-ON (Servo
ON) signal and, if the SEN signal is ON (high level), the output of the position data from the
absolute encoder to the host controller must have been completed.
*
Do not include this condition if the /S-ON (Servo ON) signal is input for the first time after the control power supply
was turned ON. In that case, when the first /S-ON signal is input, polarity detection is started immediately and the
/S-RDY signal turns ON at the completion of polarity detection.
The /S-RDY signal is allocated to CN1-29 and CN1-30 by default.
Type
Signal
Output
/S-RDY
Note: 1. Use Pn50E = n.X (/S-RDY (Servo Ready) Signal Allocation) to allocate the /S-RDY signal to another
connector pin. Refer to the following section for details.
6.1.2 Output Signal Allocations on page 6-7
2. Refer to the following section for information on the hard wire base block and the /S-RDY signal.
11.2.7 /S-RDY (Servo Ready Output) Signal on page 11-6
Setting Unit
-1
1 min
Setting Unit
1 mm/s
Connector Pin No.
Signal Status
ON (closed)
CN1-29 and CN1-
30 (default setting)
OFF (open)

6.1.7 /S-RDY (Servo Ready) Signal

Speed
Default Setting
When Enabled
20
Immediately
Speed
Default Setting
When Enabled
20
Immediately
Meaning
Ready to receive the /S-ON (Servo ON) signal.
Not ready to receive the /S-ON (Servo ON) sig-
nal.
6.1 I/O Signal Allocations
Position
Torque
Classification
Setup
Position
Force
Classification
Setup
*
6-11