en | Panel Wide Parameters
3.2.16

Alternate IPv6 DNS server IP address

Default:  ::
Selections:  0000:0000:0000:0000:0000:0000:0000:0000 to
FFFF:FFFF:FFFF:FFFF:FFFF:FFFF:FFFF:FFFF
This parameter provides an alternate IPv6 DNS server IP address.
The Alternate IPv6 Domain Name Server (DNS) address has a hexadecimal notation, which
consists of the eight groups of the address expressed separately in hexadecimal and
separated by colons. Each group has a value between 0000-FFFF.
When this is defined through the DHCP service, leave the default value. If the module fails to
obtain an address from the primary server, the Alternate IPV6 DNS server is used, if specified.
The module can use the Alternate IPv6 DNS server only when the Primary address is not the
default address.
Further information
IP Address and Domain Name formats, page 282
RPS Menu Locations
Panel Wide Parameters > Onboard Ethernet Communicator > Alternate IPv6 DNS server IP
address
3.3

Cellular Plug-in Module

3.3.1

Inbound SMS

Notice!
Important configuration information for cellular communication
Refer to Configuring for Cellular Service, page 280 for an overview and configuration
information.
Default: Yes
Selections:
Yes - Enabled
No - Disabled
This parameter enables an RPS user to start a control panel initiated download with an SMS
message.
RPS Menu Location
Panel Wide Parameters > Cellular Plug-in Module > Inbound SMSB450 Cellular > Inbound SMS
3.3.2

Session Keep Alive Period (min.)

Notice!
Important configuration information for cellular communication
Refer to Configuring for Cellular Service, page 280 for an overview and configuration
information.
Default: 0
Selections: 0 to 1000 (minutes)
This parameter sets the length of time in minutes between session keep alive reports to verify
that an idle connection is still active. This parameter is pre-configured for optimal
performance. Leave at the default setting. Default settings should only be changed for high
security UL1610 commercial listed installations requiring low signal notification.
2017.03 | 09 | F.01U.303.998
0 - Disabled. Panel does not verify the connection is active.
1 to 1000 - Enabled. Panel verifies an active connection exists.