30
en | Panel Wide Parameters
RPS Menu Location
Panel Wide Parameters > Phone and Phone Parameters > Alarm on Fail
3.1.6

Buzz on Fail

Default: No
Selections:
Notice!
UL 864 requirement for commercial fire
To comply with UL864 requirements for commercial fire systems, set this parameter to Yes
To use this Buzz on fail feature, enable phone line supervision at the  Phone Supervision Time,
page 29 parameter.
Panel-wide trouble tones are enabled and disabled for individual keypads at their Trouble
Tone parameter (Trouble Tone, page 115). The default for the Trouble Tone parameter for all
keypads is No (panel wide troubles do not sound).
RPS Menu Location
Panel Wide Parameters > Phone and Phone Parameters > Buzz On Fail
3.1.7

Two Phone Lines

Default: No
Selections:
This parameter enables the dual phone line feature.
To supervise and send reports over two separate phone lines set this parameter to Yes and
install two B430 Plug-in Telephone Communicator modules.
The B430 module plugged into the MOD-1 connector on the control panel is Phone Line 1.
The B430 module plugged into the MOD-2 connector on the control panel is Phone Line 2.
If the control panel senses that a phone line is missing (faulted) it creates a Phone Line
Missing event and uses the other phone line to send reports. The control panel logs Phone
Line Missing events.
The control panel switches between Phone Line 1 and Phone Line 2 each time it sends a Test
report. After the test report is sent, that line becomes the first to be used for sending reports.
Notice!
UL 864 requirement for commercial fire
To comply with UL 864 requirements for Commercial Fire Systems, set this parameter to Yes
when using PSTN communications.
RPS Menu Location
Panel Wide Parameters > Phone and Phone Parameters > Two Phone Lines
3.1.8

Expand Test Report

Default: No
2017.03 | 09 | F.01U.303.998
activating the alarm tone at keypads
sending alarm reports
Yes - the control activates a panel-wide trouble tone at all keypads when a phone line fail
event occurs.
No - the control does not activate the trouble tone at any keypad when a phone line fail
event occurs.
Yes - two B430 Plug-in Telephone Communicator modules are installed
No - only one or no B430 Plug-in Telephone Communicator modules are installed
Program Entry Guide