200 en | Points
This parameter allows points with the associated point index to delay a burglar alarm (non-
fire) event for the time period specified in Abort Window, page 78.
Notice!
To comply with UL standards, the total amount of time entered in Entry Delay, page 190 and
Alarm Event Abort must not exceed 1 minute.
An alarm is aborted by performing an alarm silence operation before this time elapses at a
keypad showing the burglar alarm event. When an alarm is successfully aborted, the keypad
shows an optional ALARM NOT SENT message. Refer to Abort Display, page 117 for more
information.
This parameter does not apply to fire alarms or invisible point alarms. When upgrading a non-
control panel account to a control panel account, RPS forces the default to No.
RPS Menu Location
Points > Point Indexes > Alarm Abort
10.3.29

Wireless Point Supervision Time

Default:
Selections:
This parameter sets the length of time in hours between failure events to hear from the
wireless transmitter before sending a missing event for devices configured to report to the
Wireless Receiver.
RADION keyfobs will follow the supervision rules if configured as a point device. Fire points
have a fixed supervision interval of 4 hours, regardless of Wireless Point Supervision Time
setting. If the point type is Fire, then the Wireless Point Supervision Time setting can only be
set to 4 hours.
This is an alternate supervision interval to the global System (Repeater) Supervision Time, page
253 setting.
RPS Menu Location
Points > Point Indexes > Wireless Point Supervision Time
10.3.30

Custom Function

Default: Disabled
Selections:
This specifies the custom function to be run when a point with this index faults to a short (S)
or open (O) state.
RPS Menu Location
Points > Point Indexes > Custom Function
10.3.31

Monitor Delay

Default: 00:00
Selections: 00:00, 00:01 thru 60:00
00:00 = disabled
2017.03 | 09 | F.01U.303.998
Point Index 1-2, 7-16: 24 Hours
Point Indexes 3-6: 4 Hours
None. Disable wireless point supervision.
4, 12, 24, 48, 72. Set the length of time in hours for wireless point supervision.
B9512G: Disabled, Function 128 to Function 159
B8512G: Disabled, Function 128 to Function 135
Program Entry Guide