Burg Pattern; Gas Pattern - Bosch B9512G Program Entry Manual

Security system
Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

Control Panel
Notice!
To comply with SIA CP-01 False Alarm Reduction, set this parameter to 6 minutes or higher in
all enabled areas. Refer to SIA CP-01 Verification for more information.
The output activated for this time is programmed in A# Alarm Bell, page 133.The bell output
starts as soon as the burglary alarm occurs. It shuts off the bell when the programmed number
of minutes expires. When the control panel's internal clock begins a new minute, it considers
the first minute expired. Set this parameter for two or more minutes.
RPS Menu Location
Area Wide Parameters > Area/Bell Parameters, Open/Close Options > Burg Time
4.1.18

Burg Pattern

Default: Steady
Selections:
Select the bell pattern this area uses to signal an alarm on a non-fire point.
RPS Menu Location
Area Wide Parameters > Area/Bell Parameters, Open/Close Options > Burg Pattern
4.1.19

Gas Pattern

Default: Temporal Code 4
Selections:
Select the bell pattern this area uses to signal an alarm on a non-fire point.
RPS Menu Location
Area Wide Parameters > Area/Bell Parameters, Open/Close Options > Gas Pattern
Bosch Security Systems, Inc.
Steady - steady output.
Pulsed - pulsed march time. 60 beats per minute at an even tempo (0.5 seconds on and
0.5 seconds off).
California Standard - 10 seconds audible + 5 seconds silent + 10 seconds audible + 5
seconds silent. This sequence repeats until bell time expires.
Temporal Code 3 - 0.5 seconds On, 0.5 seconds Off, 0.5 seconds On, 0.5 seconds Off, 0.5
seconds On, 1.5 seconds Off; pattern repeats. This sequence repeats for a minimum of 3
minutes with ± 10% timing tolerance. (1999 NFPA standards allow automatic silencing as
permitted by the Authority Having Jurisdiction (AHJ), and carry a minimum ring time of 5
minutes.)
Steady. Steady output.
Pulsed. Pulsed march time. 60 beats per minute at an even tempo (0.5 seconds on and
0.5 seconds
off).
California Standard. 10 seconds audible + 5 seconds silent + 10 seconds audible + 5
seconds silent. This sequence repeats until bell time expires.
Temporal Code 3. 0.5 seconds On, 0.5 seconds Off, 0.5 seconds On, 0.5 seconds Off, 0.5
seconds On, 1.5 seconds Off; pattern repeats. This sequence repeats for a minimum of 3
minutes with ± 10% timing tolerance. (1999 NFPA standards allow automatic silencing as
permitted by the Authority Having Jurisdiction (AHJ), and carry a minimum ring time of 5
minutes.)
Temporal Code 4. 0.1 seconds On, 0.1 seconds Off, 0.1 seconds On, 0.1 seconds Off, 0.1
seconds On, 0.1 seconds Off, 0.1 seconds On, 5 seconds Off; pattern repeats.
Program Entry Guide
Area Wide Parameters | en 101
2017.03 | 09 | F.01U.303.998