Control Panel
The Debounce parameter sets the length of time the control panel scans a point before
initiating an alarm. Consult the manufacturer's instructions for the device connected to the
point if you are unsure of how to set this parameter.
Bosch recommends an entry of 820 ms or higher. For Interior Follower points set Debounce to
at least 1.23 seconds.
Debounce does not apply when the point Source, page 176 is set to Wireless, IP Camera, or
Output. RPS automatically selects a dash (-) for Debounce, which indicates that Debounce is
not applicable.
RPS Menu Location
Points > Point Assignments > Debounce
10.1.8

Output

Default: 0
Selections:
Use this parameter to activate an output when the point goes into alarm.
The output does not activate for Trouble or Supervisory events. The output resets when the
originating point restores and the corresponding alarm restoration event is generated.
Notice!
Legacy BFSK Relay or Relay functionality
The point assignment parameters for many legacy Bosch control panels include a BFSK Relay
or Relay parameter for each point.
You can easily emulate BFSK Relay functionality by setting this new Output parameter to the
same output number for multiple points. You can use any output number for any number of
points.
NOTE:  To expand or collapse the list of Point numbers, use the arrows at the top of the RPS
screen.
RPS Menu Location
Points > Point Assignments > Output
10.1.9

RADION RFID (B810)

Default: - blank
Selections: 0, 11 - 167772156
A point Radio Frequency device Identification number (RFID) can be Auto-Learned through the
SDI2 bus RF receiver, or it can be entered here.
Auto-Learned RFID's can be edited for point replacement, or can be set to 0 to disable a RF
point. An RFID is a unique number assigned to a wireless device at the factory. It provides a
unique way for the wireless receiver and wireless repeaters to identify what device is
transmitting.
If an SDI2 communication device is allocated for automation communication, then it cannot be
used for central station or RPS communication.
When the Point Source is configured to Wireless, then the RFID is set to 0.
Bosch Security Systems, Inc.
6.15
B9512G: 0 to 599
B8512G: 0 to 99
Program Entry Guide
Points | en 179
2017.03 | 09 | F.01U.303.998