Control Panel
On the keypad's display, DISARM NOW appears for the duration of the time programmed
when the point is faulted in the delay event. The keypad display alternates between DISARM
NOW and the point text of the point that caused the area to enter into Entry Delay.
If this time is allowed to expire before disarming or if the point is faulted to an instant
response (I) an alarm occurs.
Make entries in five-second increments. The programmer does not allow off-increment entries.
Disarm by Passcode, page 172 activates when the last digit of the passcode is pressed. The
[ENTER] key is allowed, but not required, when entering a passcode during Entry Delay.
If a subsequent perimeter or interior follower delay point trips while the area is already in
entry delay, the control panel adjusts the delay time to the delay point with the least amount
of delay time.
When a user enters an area, a perimeter point is faulted and Entry Delay starts. If an interior
point must fault during Entry Delay to allow the user to disarm the area at a keypad, program
Point Type, page 184 as Interior Follower.
RPS Menu Location
Points > Point Indexes > Entry Delay
10.3.7

Entry Tone Off

Default: No (for all Point Indexes)
Selections:
This parameter enables/disables the entry delay warning tone for this point.
Do not set this parameter to No on points used to notify the user to disarm the system. The
possibility of false alarms increases if the entry delay warning is not used.
Entry Tone can also be turned off when programming your Entry Tone, page 116 in the keypad
section which allows you to manage the tone by keypad.
You might want to disable the entry tone in high security applications where you do not want
to annunciate entry delay.
RPS Menu Location
Points > Point Indexes > Entry Tone Off
10.3.8

Silent Bell

Default:
Selections:
This parameter determines whether the bell and keypad sounders activate upon an alarm
event for non-fire/gas points. Fire and Gas points ignore this parameter setting and always
activate the bell and sound the alarm tone at keypads when this point goes into alarm.
If you want this point to eventually ring the bell because the message failed to reach the
central station receiver, set Audible After Two Fails, page 192 to Yes.
Bosch Security Systems, Inc.
Yes. Disable entry delay tone when this point is faulted to the delay response.
No. A tone sounds at keypads when this point initiates entry delay.
Point Index 2: Yes
All other Point Indexes: No
Yes   Activate the Silent Alarm, page 137 output when this point goes into alarm; Do not
activate the Alarm Bell output or keypad alarm sounders. This setting only applies to non-
fire/gas points.
No    Activate the Fire Bell, page 133, Gas Bell, page 137 or Alarm Bell, page 133 output and
sound the alarm tone at keypads when this point goes into alarm. If this is a fire point, it
activates the Fire Bell. If this is a gas point, it activates the Gas Bell, otherwise, it
activates the Alarm Bell. The amount of time and pattern of the output activation is
programmed by area.